ABB / Power-One Aurora error codes explained

What 28 ABB / Power-One Aurora inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
E001Fault
Input OC

The alarm appears when the in- Check whether the composition of the PV array al-

What you can do

  • Check solar generation in the app compared with similar days
  • Do not touch the DC isolators, cables or connectors, and don't go on the roof
  • If it doesn't clear by itself, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E002Fault
Input OV

This alarm is indicated when the Measure the input voltage in the inverter with a

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E003Warning
No Parameters

The main microcontroller is un- This is an error inside the inverter that cannot be

What you can do

  • Check the monitoring app for the alarm and whether export/consumption readings look wrong
  • Restart your home router if the meter talks over Wi-Fi or LAN
  • Call your installer - meter and CT wiring is inside the switchboard and must be checked by a licensed electrician

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E004Fault
Bulk OV

Error inside the inverter. The The alarm can be triggered by causes external to

What you can do

  • Check the app - the battery may show as offline or with no state of charge
  • Restart the system once using the shutdown and start-up steps in your owner's manual (battery last off, first on, unless your manual says otherwise)
  • If the alarm comes back, call your installer - battery communication cables must be checked by them

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E013Fault
Wrong Mode

The alarm is generated only when Make sure the setting of the “IN MODE” switch has

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E014Warning
Over Temp.

Internal inverter temperature Wait for the temperatures to which the inverter is

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E015Fault
Bulk Cap Fail Bulk capacitor fail-

Error inside the inverter regarding Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E016Fault
Inverter Fail Inverter

The alarm is generated when a Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E017Fault
Start Timeout Inverter start- up timeout

Error inside the inverter regarding If the alarm is present early in the morning it could

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E022Fault
Self-Test Error 4 timeout

Time taken to execute the au- Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E023Warning
DC inj error range

The error is generated if the di- If the grid voltage is strongly distorted, report this

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E024Fault
Internal error service.

Error inside the inverter Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E029Fault
Error Meas Z Fault

Error in the internal measurement Error inside the inverter that cannot be checked

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E030Safety-Critical
Error Meas Ileak ILeak Fault

Error in the internal measurement This is an error inside the inverter that cannot be

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E031Fault
Error Read V

Measurement of the internal volt- Check the grid conditions for instabilities caused by

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E032Fault
Error Read I Wrong I Measure

Measurement of the output volt- This is an error inside the inverter that cannot be

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E033Warning
UTH

Alarm is triggered when internal Wait for the temperatures to which the inverter is

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E034Fault
Interlock fail IGBT not ready service.

Error inside the inverter Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E056Warning
external box)

Excessive temperature mea- Check that the inverter is not exposed to direct

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E057Fault
E057

Input voltage (Vin) higher than Measure the input voltage inside the inverter

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
E058Fault
error

The error occurs if the difference Error inside the inverter that cannot be checked ex-

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W001Info
Sun Low

Insufficient sunlight. Wrong con- Check the inverter input voltage.

What you can do

  • This is normal at dawn, dusk or in heavy cloud
  • If it shows in full sun, check the app for low generation and look for new shading from the ground (don't go on the roof)
  • If generation stays low on sunny days, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W002Info
Input UV

Insufficient sunlight Wrong con- Check the inverter input voltage.

What you can do

  • This is normal at dawn, dusk or in heavy cloud
  • If it shows in full sun, check the app for low generation and look for new shading from the ground (don't go on the roof)
  • If generation stays low on sunny days, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W003Info
Grid Fail

This error warning appears dur- Check the grid voltage on the inverter. If absent,

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W019Warning
open placed.

Overvoltage surge arresters situ- Look at the inspection window present on each

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W022Fault
Reactive mode changed notification only

Variation in the means of manag- Notification of change that is saved in the historical

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W023Fault
W023

Variation of the inverter’s date Notification of change that is saved in the historical

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter
W024Fault
W024

Zeroing of the statistical energy Notification of change that is saved in the historical

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) · Guide only. All work must be done by a licensed electrician.

PVI-3.0/3.6/3.8/4.2-TL (Aurora UNO) Inverter

Common ABB / Power-One Aurora questions

What does ABB / Power-One Aurora E001 "Input OC" mean?

The alarm appears when the in- Check whether the composition of the PV array al- Check solar generation in the app compared with similar days This is a guide only; any electrical work must be done by a licensed electrician.

What does ABB / Power-One Aurora E002 "Input OV" mean?

This alarm is indicated when the Measure the input voltage in the inverter with a Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does ABB / Power-One Aurora E004 "Bulk OV" mean?

Error inside the inverter. The The alarm can be triggered by causes external to Check the app - the battery may show as offline or with no state of charge This is a guide only; any electrical work must be done by a licensed electrician.

What does ABB / Power-One Aurora E013 "Wrong Mode" mean?

The alarm is generated only when Make sure the setting of the “IN MODE” switch has Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does ABB / Power-One Aurora E015 "Bulk Cap Fail Bulk capacitor fail-" mean?

Error inside the inverter regarding Error inside the inverter that cannot be checked ex- Note the code, date and time and check the monitoring app This is a guide only; any electrical work must be done by a licensed electrician.

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

ABB / Power-One Aurora is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides

Get a quote Call