GoodWe ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 error codes explained

What 159 GoodWe ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
F01Warning
Grid Power Outage

The inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup).

What you can do

  • Check whether the rest of the house (or your neighbours) has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar supply main switch or inverter breaker. Only reset it once. If it trips again, leave it off and call an electrician
  • Wait. Once normal grid power is back, the inverter normally reconnects by itself after its safety checks (often a few minutes)
  • If grid power is normal but the alarm stays, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F02Warning
Grid Overvoltage Protection

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F03Warning
Grid Undervoltage Protection

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F04Warning
Grid Rapid Overvoltage Protection

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F05Warning
10min Overvoltage Protection

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F06Warning
Grid Overfrequency

Grid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require.

What you can do

  • Wait for automatic reconnection
  • If it happens often, record the times and contact us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F07Warning
Grid Underfrequency

Grid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require.

What you can do

  • Wait for automatic reconnection
  • If it happens often, record the times and contact us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F08Warning
Grid Frequency Instability

Grid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require.

What you can do

  • Wait for automatic reconnection
  • If it happens often, record the times and contact us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F09Warning
Anti-islanding Protection

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F10Warning
LVRT Undervoltage Fault

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F11Warning
HVRT Overvoltage

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F12Critical
30mA GFCI Protection

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F13Critical
60mA GFCI Protection

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F14Critical
150mA GFCI Protection

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F15Critical
GFCI Gradual Change Protection

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F16Fault
DCI Level 1 Protection

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F17Fault
DCI Level 2 Protection

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F18Critical
Low Insulation Resistance

The inverter measured low insulation resistance between the PV strings or battery port and earth. GoodWe notes that Australian/NZ units raise an earth fault alarm for this. Treat it as an electrical safety issue.

What you can do

  • Do not touch panels, DC cables, rooftop isolators or the inverter's DC connectors
  • If it clears by itself after the weather dries out, still report it, because repeated alarms point to a developing fault
  • Book an electrician or call us. An insulation test needs specialist equipment
  • If you see smoke, burn marks or smell burning, keep clear and call 000

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F19Critical
Grounding Abnormal

The inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety.

What you can do

  • Do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down. Call a licensed electrician or us to test the earthing

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F20Warning
Hardware Anti-backfeed Protection

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F21Fault
Internal Comm Loss

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F22Warning
Generator Waveform Detection Fault

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F23Warning
Generator Abnormal Connection

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F24Warning
Generator Voltage Low

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F25Warning
Generator Voltage High

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F26Warning
Generator Frequency Low

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F27Warning
Generator Frequency High

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F28Fault
Parallel I/O Self-check Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F29Fault
Parallel Grid Line Reversed

The inverter has detected an AC wiring problem, for example active and neutral swapped or a connection made the wrong way round.

What you can do

  • Do not touch any wiring
  • Leave the system as it is and book a licensed electrician (or call us)

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F30Fault
AC HCT check Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F31Fault
GFCI HCT Check Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F32Fault
Inverter Internal Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F33Fault
Flash Read/Write Error

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F34Fault
AFCI Check Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F35Warning
Cabinet Overtemperature

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F36Fault
Bus Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F37Fault
PV Input Overvoltage

The DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter.

What you can do

  • Do not touch the DC isolator or cables unless the manufacturer's owner shutdown tells you to
  • Call us. The string design needs to be checked by a licensed installer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F38Fault
PV Continuous Hardware Overcurrent

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F39Fault
PV Continuous Software Overcurrent

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F41Warning
Generator Port Overload

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F42Critical
DC Arcing Failure (String 1-n) n: Determined by the actual number of inverter strings.

The inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution.

What you can do

  • Do not reset it repeatedly and do not touch DC cables or isolators
  • If you see smoke or flames or smell burning, keep clear and call 000
  • Call us or a licensed electrician to inspect the DC wiring before the system is restarted

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F43Warning
Grid Waveform Abnormal

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F44Warning
Grid Phase Loss

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F45Warning
Grid Voltage Imbalance

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F46Warning
Grid Phase Sequence Failure

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F47Warning
Grid Rapid Shutdown Protection

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F48Warning
Grid Neutral Wire Loss (Split-phase Grid)

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F49Critical
L-PE Short Circuit

The inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety.

What you can do

  • Do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down. Call a licensed electrician or us to test the earthing

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F50Fault
DCV Level 1 Protection

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F51Fault
DCV Level 2 Protection

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F52Critical
Leakage Current (GFCI) Multiple Fault Shutdown

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F53Critical
DC Arcing (AFCI) Multiple Fault Shutdown

The inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution.

What you can do

  • Do not reset it repeatedly and do not touch DC cables or isolators
  • If you see smoke or flames or smell burning, keep clear and call 000
  • Call us or a licensed electrician to inspect the DC wiring before the system is restarted

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F54Info
External Communication Link Failure

A monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating.

What you can do

  • Restart your home router and check it reaches the inverter location
  • If you changed router or Wi-Fi password, the dongle needs reconfiguring (see the manufacturer's app guide or ask us)
  • If generation looks normal but the alarm persists, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F55Warning
Back-up Port Overload Fault

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F56Warning
Back-up Port Overvoltage Fault

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F57Fault
External Box Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F58Warning
CT Loss Fault

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F59Fault
Parallel CAN Communication Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F60Warning
Parallel Back-up Connection Reversed

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F61Fault
Inverter Soft Start Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F62Fault
AC HCT Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F63Fault
GFCI HCT Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F64Fault
Inverter Internal Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F65Warning
AC Terminal Overtemperature

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F66Warning
INV Module Overtemperature

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F67Warning
Boost Module Overtemperature

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F68Warning
AC Capacitor Overtemperature

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F69Fault
PV IGBT Short Circuit Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F70Fault
PV IGBT Open Circuit Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F71Fault
NTC Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F72Fault
PWM Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F73Fault
CPU Interrupt Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F74Fault
Microelectronics Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F75Fault
PV HCT Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F76Fault
1.5V Reference Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F77Fault
0.3V Reference Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F78Fault
CPLD Version Recognition Error

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F79Fault
CPLD Communication Fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F80Fault
Model Identification Fault

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F81Fault
P-Bus Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F82Fault
N-Bus Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F83Fault
Bus Overvoltage (Sub CPU1)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F84Fault
P-Bus Overvoltage (Sub CPU1)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F85Fault
N-Bus Overvoltage (Sub CPU1)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F86Fault
Bus Overvoltage (Sub CPU2)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F87Fault
P-Bus Overvoltage (Sub CPU2)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F88Fault
N-Bus Overvoltage (Sub CPU2)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F89Fault
P-Bus Overvoltage (CPLD)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F90Fault
N-Bus Overvoltage (CPLD)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F91Fault
FlyCap Software Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F92Fault
FlyCap Hardware Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F93Fault
FlyCap Undervoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F94Fault
FlyCap Precharge Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F95Fault
FlyCap Precharge Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F101Fault
Battery 1 Precharge fault

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F102Fault
Battery 1 Relay Failure

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F103Fault
Battery 1 Connection Overvoltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F104Fault
Battery 2 Precharge fault

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F105Fault
Battery 2 Relay Failure

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F106Fault
Battery 2 Connection Overvoltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F107Fault
On-grid PWM Sync Failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F108Fault
DSP Communication fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F109Fault
External STS fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F110Warning
Export Limit Protection

The inverter has stopped or limited export to stay within the export limit set for your site, usually because meter readings dropped out or power briefly flowed the wrong way.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F111Warning
Bypass Overload

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F112Warning
Black Start Failure

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F113Warning
Offgrid AC Ins Volt High

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F114Fault
Relay Failure2

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F115Fault
SVG Precharge Disabled

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F116Fault
Nighttime SVG PID Prevention fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F117Fault
DSP Version Recognition Error

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F118Fault
MOS Continuous Overvoltage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F119Fault
Bus Short Circuit fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F120Fault
Bus Sampling Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F121Fault
DC Side Sampling Abnormality

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F122Fault
PV Access Mode Setting Error

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F123Fault
Multi-channel PV Phase Error

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F124Fault
Battery 1 Reverse Connection fault

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F125Fault
Battery 2 Reverse Connection fault

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F126Fault
Abnormal Battery Connection

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F127Critical
BAT Overtemperature

The battery (or one of its internal parts) is above its safe temperature, so charging or discharging is limited or stopped to protect it.

What you can do

  • Keep clear and do not open or touch the battery
  • If you notice smoke, a burning or chemical smell, hissing, swelling or leaking, leave the area, keep others away and call 000
  • Otherwise, make sure the space around the battery is clear and shaded, and call us or a licensed electrician to check it

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F128Fault
Ref Voltage Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F129Warning
Cabinet Under Temperature

The inverter temperature is below its operating range.

What you can do

  • Wait for temperatures to rise. It should recover by itself
  • If it persists in normal weather, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F130Fault
AC Side SPD fault

A surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge.

What you can do

  • Don't open the inverter
  • Call us. SPDs must be replaced by a licensed electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F131Fault
DC Side SPD fault

A surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge.

What you can do

  • Don't open the inverter
  • Call us. SPDs must be replaced by a licensed electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F132Warning
Internal Fan Abnormal

A cooling fan isn't working properly, which can make the unit run hot and reduce output.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call us to arrange a fan check or replacement

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F133Warning
External Fan Abnormal

A cooling fan isn't working properly, which can make the unit run hot and reduce output.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call us to arrange a fan check or replacement

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F134Fault
PID Diagnosis Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F135Info
Trip-Switch Trip Warning

The system has received a shutdown or control signal, or a protective input has been triggered (for example an emergency stop, demand response or external switch).

What you can do

  • Check whether anyone operated an emergency stop or shutdown switch on purpose
  • If so, follow the manual to release it only when it is safe
  • If nobody did, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F136Fault
Historical PV IGBT Short Circuit Warning

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F139Fault
Flash Read/Write Error Warning

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F140Warning
Meter Comm Loss

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F141Warning
PV Panel Type Identification Failure

One solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue.

What you can do

  • From the ground, check for new shading (trees, new structures) or obvious debris
  • Compare string readings in your monitoring app if available
  • Book a service check if it continues

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F142Warning
PV String Mismatch

One solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue.

What you can do

  • From the ground, check for new shading (trees, new structures) or obvious debris
  • Compare string readings in your monitoring app if available
  • Book a service check if it continues

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F143Warning
CT Not Connected

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F144Warning
CT Reverse Connection

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F145Critical
PE Loss

The inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety.

What you can do

  • Do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down. Call a licensed electrician or us to test the earthing

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F146Warning
String Terminal High Temperature (String 1~8)

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F147Warning
String Terminal High Temperature (String 9~16)

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F148Warning
String Terminal High Temperature (String 17~20)

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F149Fault
Historical PV Reverse Connection Warning (String 33~48)

A solar string or the battery appears to be connected with positive and negative swapped.

What you can do

  • Do not touch any DC wiring
  • Call us or a licensed electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F150Fault
Battery 1 Low Voltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F151Fault
Battery 2 Low Voltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F152Info
Low Voltage of Battery Power

The battery's state of charge or voltage is low, so the system has stopped discharging it to protect the cells.

What you can do

  • Allow it to recharge from solar (or the grid, if your settings allow)
  • Check the app for other alarms that could be stopping charging
  • If it stays low for days in good sun, call us. Batteries left flat for long periods can be damaged

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F153Fault
Battery 1 High Voltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F154Fault
Battery 2 High Voltage

The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation.

What you can do

  • Do not open the battery or touch its terminals
  • Note the exact alarm text and time from the app
  • Call us. Battery faults should be handled by the installer or manufacturer

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F155Critical
Online Low Insulation Resistance

The inverter measured low insulation resistance between the solar/battery DC circuits and earth. In Australia this is treated as an earth fault alarm, and the system must be checked by a licensed electrician.

What you can do

  • Do not touch panels, DC cables, rooftop isolators or the inverter's DC connectors
  • If it clears by itself after the weather dries out, still report it, because repeated alarms point to a developing fault
  • Book an electrician or call us. An insulation test needs specialist equipment
  • If you see smoke, burn marks or smell burning, keep clear and call 000

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F156Warning
Micro-grid Overload Warning

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F157Fault
Manual Reset

The system has stopped and is waiting for a manual reset. GoodWe gives no further detail in the manual, so treat it as needing a service check.

What you can do

  • Note the time and any other alarms in the app
  • Call us to arrange a check

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F158Warning
Generator Phase Sequence Abnormal

A problem was detected with a connected generator input (voltage, frequency, wiring or start-up).

What you can do

  • Check the generator itself (fuel, its own alarms)
  • Call us to check the generator integration

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F159Fault
Multiplexed Port Configuration Abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F160Warning
EMS Forced Off-grid

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F161Warning
Passive Anti-islanding Protection

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F162Warning
Grid Type Fault

The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F163Warning
Grid Phase Instability

The rate of change of the grid voltage phase was outside what your local grid standard allows, so the inverter disconnected.

What you can do

  • Check whether you have a partial power outage (some circuits or phases off)
  • Wait for automatic reconnection after the grid returns to normal
  • If it persists or started after electrical work, call us

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F40 / F98Fault
String Reverse Connection (String 1-n)

A solar string or the battery appears to be connected with positive and negative swapped.

What you can do

  • Do not touch any DC wiring
  • Call us or a licensed electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F96 / F97Fault
String Overcurrent (String 1-n)

Current on one or more solar strings is above the limit, or the string current sensor is reading abnormally.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F99 / F100Warning
String Missing (String 1-n)

The inverter sees no input from a string, and GoodWe points to an open string fuse (on models with string fuses).

What you can do

  • From the ground, check for new shading (trees, new structures) or obvious debris
  • Compare string readings in your monitoring app if available
  • Book a service check if it continues

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter
F137 / F138Fault
Historical PV Reverse Connection Warning (String 1-n)

The inverter has a record that a string was connected with reversed polarity at some point, which caused the trip switch to operate. A technician needs to check the string before the warning is cleared in the app.

What you can do

  • Do not touch any DC wiring
  • Call us or a licensed electrician

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician.

ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 Inverter

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

GoodWe is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides