GoodWe ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 error codes explained
What 159 GoodWe ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.
Safety first: never open the switchboard, remove covers, or pull apart or disconnect the inverter, batteries, isolators or wiring. Only use the switches and buttons described here. Anything else must be done by a licensed electrician. Call 1300 209 503 or book a service request.
| Code | Message & meaning |
|---|---|
| F01Warning |
Grid Power OutageThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F02Warning |
Grid Overvoltage ProtectionThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F03Warning |
Grid Undervoltage ProtectionThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F04Warning |
Grid Rapid Overvoltage ProtectionThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F05Warning |
10min Overvoltage ProtectionThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F06Warning |
Grid OverfrequencyGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F07Warning |
Grid UnderfrequencyGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F08Warning |
Grid Frequency InstabilityGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F09Warning |
Anti-islanding ProtectionThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F10Warning |
LVRT Undervoltage FaultThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F11Warning |
HVRT OvervoltageThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F12Critical |
30mA GFCI ProtectionThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F13Critical |
60mA GFCI ProtectionThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F14Critical |
150mA GFCI ProtectionThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F15Critical |
GFCI Gradual Change ProtectionThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F16Fault |
DCI Level 1 ProtectionThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F17Fault |
DCI Level 2 ProtectionThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F18Critical |
Low Insulation ResistanceThe inverter measured low insulation resistance between the PV strings or battery port and earth. GoodWe notes that Australian/NZ units raise an earth fault alarm for this. Treat it as an electrical safety issue. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F19Critical |
Grounding AbnormalThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F20Warning |
Hardware Anti-backfeed ProtectionThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F21Fault |
Internal Comm LossThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F22Warning |
Generator Waveform Detection FaultA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F23Warning |
Generator Abnormal ConnectionA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F24Warning |
Generator Voltage LowA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F25Warning |
Generator Voltage HighA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F26Warning |
Generator Frequency LowA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F27Warning |
Generator Frequency HighA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F28Fault |
Parallel I/O Self-check AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F29Fault |
Parallel Grid Line ReversedThe inverter has detected an AC wiring problem, for example active and neutral swapped or a connection made the wrong way round. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F30Fault |
AC HCT check AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F31Fault |
GFCI HCT Check AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F32Fault |
Inverter Internal FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F33Fault |
Flash Read/Write ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F34Fault |
AFCI Check FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F35Warning |
Cabinet OvertemperatureThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F36Fault |
Bus OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F37Fault |
PV Input OvervoltageThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F38Fault |
PV Continuous Hardware OvercurrentThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F39Fault |
PV Continuous Software OvercurrentThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F41Warning |
Generator Port OverloadA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F42Critical |
DC Arcing Failure (String 1-n) n: Determined by the actual number of inverter strings.The inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F43Warning |
Grid Waveform AbnormalThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F44Warning |
Grid Phase LossThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F45Warning |
Grid Voltage ImbalanceThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F46Warning |
Grid Phase Sequence FailureThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F47Warning |
Grid Rapid Shutdown ProtectionThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F48Warning |
Grid Neutral Wire Loss (Split-phase Grid)The inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F49Critical |
L-PE Short CircuitThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F50Fault |
DCV Level 1 ProtectionThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F51Fault |
DCV Level 2 ProtectionThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F52Critical |
Leakage Current (GFCI) Multiple Fault ShutdownThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F53Critical |
DC Arcing (AFCI) Multiple Fault ShutdownThe inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F54Info |
External Communication Link FailureA monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F55Warning |
Back-up Port Overload FaultThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F56Warning |
Back-up Port Overvoltage FaultThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F57Fault |
External Box FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F58Warning |
CT Loss FaultThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F59Fault |
Parallel CAN Communication AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F60Warning |
Parallel Back-up Connection ReversedThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F61Fault |
Inverter Soft Start FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F62Fault |
AC HCT FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F63Fault |
GFCI HCT FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F64Fault |
Inverter Internal FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F65Warning |
AC Terminal OvertemperatureThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F66Warning |
INV Module OvertemperatureThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F67Warning |
Boost Module OvertemperatureThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F68Warning |
AC Capacitor OvertemperatureThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F69Fault |
PV IGBT Short Circuit FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F70Fault |
PV IGBT Open Circuit FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F71Fault |
NTC AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F72Fault |
PWM AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F73Fault |
CPU Interrupt AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F74Fault |
Microelectronics FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F75Fault |
PV HCT FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F76Fault |
1.5V Reference AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F77Fault |
0.3V Reference AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F78Fault |
CPLD Version Recognition ErrorThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F79Fault |
CPLD Communication FaultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F80Fault |
Model Identification FaultThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F81Fault |
P-Bus OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F82Fault |
N-Bus OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F83Fault |
Bus Overvoltage (Sub CPU1)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F84Fault |
P-Bus Overvoltage (Sub CPU1)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F85Fault |
N-Bus Overvoltage (Sub CPU1)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F86Fault |
Bus Overvoltage (Sub CPU2)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F87Fault |
P-Bus Overvoltage (Sub CPU2)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F88Fault |
N-Bus Overvoltage (Sub CPU2)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F89Fault |
P-Bus Overvoltage (CPLD)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F90Fault |
N-Bus Overvoltage (CPLD)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F91Fault |
FlyCap Software OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F92Fault |
FlyCap Hardware OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F93Fault |
FlyCap UndervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F94Fault |
FlyCap Precharge FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F95Fault |
FlyCap Precharge AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F101Fault |
Battery 1 Precharge faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F102Fault |
Battery 1 Relay FailureThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F103Fault |
Battery 1 Connection OvervoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F104Fault |
Battery 2 Precharge faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F105Fault |
Battery 2 Relay FailureThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F106Fault |
Battery 2 Connection OvervoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F107Fault |
On-grid PWM Sync FailureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F108Fault |
DSP Communication faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F109Fault |
External STS faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F110Warning |
Export Limit ProtectionThe inverter has stopped or limited export to stay within the export limit set for your site, usually because meter readings dropped out or power briefly flowed the wrong way. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F111Warning |
Bypass OverloadThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F112Warning |
Black Start FailureThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F113Warning |
Offgrid AC Ins Volt HighThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F114Fault |
Relay Failure2The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F115Fault |
SVG Precharge DisabledThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F116Fault |
Nighttime SVG PID Prevention faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F117Fault |
DSP Version Recognition ErrorThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F118Fault |
MOS Continuous OvervoltageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F119Fault |
Bus Short Circuit faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F120Fault |
Bus Sampling AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F121Fault |
DC Side Sampling AbnormalityThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F122Fault |
PV Access Mode Setting ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F123Fault |
Multi-channel PV Phase ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F124Fault |
Battery 1 Reverse Connection faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F125Fault |
Battery 2 Reverse Connection faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F126Fault |
Abnormal Battery ConnectionThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F127Critical |
BAT OvertemperatureThe battery (or one of its internal parts) is above its safe temperature, so charging or discharging is limited or stopped to protect it. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F128Fault |
Ref Voltage AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F129Warning |
Cabinet Under TemperatureThe inverter temperature is below its operating range. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F130Fault |
AC Side SPD faultA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F131Fault |
DC Side SPD faultA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F132Warning |
Internal Fan AbnormalA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F133Warning |
External Fan AbnormalA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F134Fault |
PID Diagnosis AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F135Info |
Trip-Switch Trip WarningThe system has received a shutdown or control signal, or a protective input has been triggered (for example an emergency stop, demand response or external switch). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F136Fault |
Historical PV IGBT Short Circuit WarningThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F139Fault |
Flash Read/Write Error WarningThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F140Warning |
Meter Comm LossThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F141Warning |
PV Panel Type Identification FailureOne solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F142Warning |
PV String MismatchOne solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F143Warning |
CT Not ConnectedThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F144Warning |
CT Reverse ConnectionThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F145Critical |
PE LossThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F146Warning |
String Terminal High Temperature (String 1~8)The inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F147Warning |
String Terminal High Temperature (String 9~16)The inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F148Warning |
String Terminal High Temperature (String 17~20)The inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F149Fault |
Historical PV Reverse Connection Warning (String 33~48)A solar string or the battery appears to be connected with positive and negative swapped. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F150Fault |
Battery 1 Low VoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F151Fault |
Battery 2 Low VoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F152Info |
Low Voltage of Battery PowerThe battery's state of charge or voltage is low, so the system has stopped discharging it to protect the cells. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F153Fault |
Battery 1 High VoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F154Fault |
Battery 2 High VoltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F155Critical |
Online Low Insulation ResistanceThe inverter measured low insulation resistance between the solar/battery DC circuits and earth. In Australia this is treated as an earth fault alarm, and the system must be checked by a licensed electrician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F156Warning |
Micro-grid Overload WarningThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F157Fault |
Manual ResetThe system has stopped and is waiting for a manual reset. GoodWe gives no further detail in the manual, so treat it as needing a service check. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F158Warning |
Generator Phase Sequence AbnormalA problem was detected with a connected generator input (voltage, frequency, wiring or start-up). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F159Fault |
Multiplexed Port Configuration AbnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F160Warning |
EMS Forced Off-gridThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F161Warning |
Passive Anti-islanding ProtectionThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F162Warning |
Grid Type FaultThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F163Warning |
Grid Phase InstabilityThe rate of change of the grid voltage phase was outside what your local grid standard allows, so the inverter disconnected. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F40 / F98Fault |
String Reverse Connection (String 1-n)A solar string or the battery appears to be connected with positive and negative swapped. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F96 / F97Fault |
String Overcurrent (String 1-n)Current on one or more solar strings is above the limit, or the string current sensor is reading abnormally. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F99 / F100Warning |
String Missing (String 1-n)The inverter sees no input from a string, and GoodWe points to an open string fuse (on models with string fuses). What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
| F137 / F138Fault |
Historical PV Reverse Connection Warning (String 1-n)The inverter has a record that a string was connected with reversed polarity at some point, which caused the trip switch to operate. A technician needs to check the string before the warning is cleared in the app. What you can do
ET/BT G20 hybrid (ESA) incl. GW9.999K-ETA-G20 · Guide only. All work must be done by a licensed electrician. |
No codes match. Try fewer characters, or ask us.
Need help with this fault?
Get a licensed electrician to call you back.