SAJ H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) error codes explained
What 83 SAJ H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.
Safety first: never open the switchboard, remove covers, or pull apart or disconnect the inverter, batteries, isolators or wiring. Only use the switches and buttons described here. Anything else must be done by a licensed electrician. Call 1300 209 503 or book a service request.
| Code | Message & meaning |
|---|---|
| 1Fault |
Master Relay ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 2Fault |
Master EEPROM ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 3Warning |
Master Temperature High ErrorThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 4Warning |
Master Temperature Low ErrorThe inverter temperature is below its operating range. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 5Fault |
Lost Communication M<->SThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 6Fault |
GFCI Device ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 7Fault |
DCI Device ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 8Fault |
Current Sensor ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 9Warning |
Master Phase1 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 10Warning |
Master Phase1 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 11Warning |
Master Phase2 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 12Warning |
Master Phase2 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 13Warning |
Master Phase3 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 14Warning |
Master Phase3 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 15Warning |
Grid Voltage 10Min HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 16Warning |
OffGrid Output Voltage LowThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 17Warning |
OffGrid Output Short CircuitThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 18Warning |
Master Grid Frequency HighGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 19Warning |
Master Grid Frequency LowGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 21Fault |
Phase1 DCV ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 22Fault |
Phase2 DCV ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 23Fault |
Phase3 DCV ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 24Warning |
Master No Grid ErrorThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 27Critical |
GFCI ErrorThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 28Fault |
Phase1 DCI ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 29Fault |
Phase2 DCI ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 30Fault |
Phase3 DCI ErrorThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. (Phase 2/3 codes apply to three-phase models.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 31Critical |
ISO ErrorInsulation resistance between the solar circuits and earth is too low. SAJ notes that on this model an earth fault alarm turns the LED ring red and shows error <31> in the eSAJ Home app. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 32Fault |
Bus Voltage Balance ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 33Fault |
Master Bus Voltage HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 34Fault |
Master Bus Voltage LowThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 35Warning |
Master Grid Phase ErrorThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 36Fault |
Master PV Voltage High ErrorThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 37Warning |
Master Islanding ErrorThe inverter saw something abnormal about the grid supply (for example phase loss, imbalance, waveform distortion or loss of mains), so it disconnected as a safety measure. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 38Fault |
Master HW Bus Voltage HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 39Fault |
Master HW PV Current HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 40Fault |
Master Self-Test FailedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 41Fault |
HW Inv Current HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 42Fault |
Master AC SPD ErrorA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 43Fault |
Master DC SPD ErrorA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 44Critical |
Master Grid NE Voltage ErrorThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 45Warning |
Master Fan1 ErrorA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 46Warning |
Master Fan2 ErrorA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 47Warning |
Master Fan3 ErrorA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 48Warning |
Master Fan4 ErrorA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 49Warning |
Lost Communication between Master and MeterThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 50Fault |
Lost Communication between M<->SThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 51Warning |
Lost Communication between inverter and Grid MeterThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 52Info |
HMI EEPROM ErrorA monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 53Info |
HMI RTC ErrorA monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 54Fault |
BMS Device ErrorThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 55Fault |
BMS Lost.ConnThe inverter and battery (or parts inside the battery) have stopped talking to each other, so the battery may stop charging or discharging. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 56Warning |
CT Device ErrThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 57Fault |
AFCI Lost Com.ErrThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 59Warning |
Lost communication between inverter and PV MeterThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 61Warning |
Slave Phase1 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 62Warning |
Slave Phase1 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 63Warning |
Slave Phase2 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 64Warning |
Slave Phase2 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 65Warning |
Slave Phase3 Voltage HighThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 66Warning |
Slave Phase3 Voltage LowThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. (Phase 2/3 codes apply to three-phase models.) ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 67Warning |
Slave Frequency HighGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 68Warning |
Slave Frequency LowGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 73Warning |
Slave No Grid ErrorThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 74Fault |
Slave PV Input Mode ErrorThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 75Fault |
Slave HW PV Curr HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 76Fault |
Slave PV Voltage High ErrorThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 77Fault |
Slave HW Bus Volt HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. ("Slave" refers to the inverter's secondary/redundant monitoring processor.) What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 81Fault |
Lost Communication D<->CThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 83Fault |
Master Arc Device ErrorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 84Fault |
Master PV Mode ErrorThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 85Fault |
Authority expiresThe inverter reports that an authorisation/licence period has expired. SAJ gives no further detail. This code appears in the three-phase H2-T2 AU manual, not in the single-phase S2 list. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 86Info |
DRM0 ErrorThe DRM0 (demand response mode 0) input has been activated or its wiring/link is open. DRM0 tells the inverter to disconnect from the grid. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 87Critical |
Master Arc ErrorThe inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 88Fault |
Master SW PV Current HighThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 89Fault |
Battery Voltage HighThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 90Fault |
Battery Current HighThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 91Fault |
Battery Charge Voltage HighThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 92Warning |
Battery OverLoadThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 93Fault |
Battery SoftConnet TimeOutThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 94Warning |
Output OverLoadThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 95Fault |
Battery Open Circuit ErrorThe inverter and battery (or parts inside the battery) have stopped talking to each other, so the battery may stop charging or discharging. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
| 96Info |
Battery Discharge Voltage LowThe battery's state of charge or voltage is low, so the system has stopped discharging it to protect the cells. What you can do
H2 hybrid series (H2-S2 single-phase / H2-T2 three-phase, AU) · Guide only. All work must be done by a licensed electrician. |
No codes match. Try fewer characters, or ask us.
Need help with this fault?
Get a licensed electrician to call you back.
Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.
Or call 1300 209 503
Sources
Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.
- SAJ H2-(3K-6K)-S2 User Manual (AU) V1.1, ch. 7 Troubleshooting (code list identical in H2-(5K-10K)-T2 AU manual V1.4 except where noted)
- SAJ H2-(5K-10K)-T2 User Manual (AU) V1.4, ch. 7
SAJ is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides