SolarEdge Commercial three-phase inverters error codes explained

What 78 SolarEdge Commercial three-phase inverters inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
8x3Warning
Night Mode is an inverter status indicating that the input voltage is below 6V DC

Night Mode is an inverter status indicating that the input voltage is below 6V DC.

What you can do

  • This is normal at dawn, dusk, in heavy cloud or when panels are shaded
  • No action needed if it clears once the sun is up
  • If it shows in full sun, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x10Fault
Communication

Communication

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x11Fault
Unexpected Mode

Unexpected Mode

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x12Fault
Vf ESR meas

Vf ESR meas

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x13Info
Reset\Stop

Reset\Stop

What you can do

  • No action needed - this is a status message, not a fault
  • If it stays for a long time or the system isn't producing when it should, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x16Fault
Main Capacitor estimation event

Main Capacitor estimation event

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x18Fault
RSD Error

RSD Error

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x19Fault
AC voltage surge

AC voltage surge. If the fault persists.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1AFault
AC voltage surge

AC voltage surge.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1BFault
AC voltage surge

AC voltage surge.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1CFault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1DFault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1EFault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x1FFault
Grid voltage is above the country limit

Grid voltage is above the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x20Fault
Grid voltage is above the country limit

Grid voltage is above the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x21Fault
Grid voltage is above the country limit

Grid voltage is above the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x22Fault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x23Fault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x24Fault
Grid Voltage is below the country limit

Grid Voltage is below the country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x25Fault
Grid voltage above country limit

Grid voltage above country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x26Fault
Grid voltage below country limit

Grid voltage below country limit.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x27Fault
If the error flags on all three phases at the same time, there is most likely a DC related

If the error flags on all three phases at the same time, there is most likely a DC related issue on site.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x29Fault
If the error flags on all three phases at the same time, there is most likely a DC related

If the error flags on all three phases at the same time, there is most likely a DC related issue on site.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x2AFault
If the error flags on all three phases at the same time, there is most likely a DC related

If the error flags on all three phases at the same time, there is most likely a DC related issue on site.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x2BCritical
Ground faults may occur due to insufficient insulation to the ground

Ground faults may occur due to insufficient insulation to the ground.

What you can do

  • Keep clear - do not touch the panels, rooftop isolators, DC cables or the inverter
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x2CCritical
Ground faults may occur due to insufficient insulation to the ground

Ground faults may occur due to insufficient insulation to the ground.

What you can do

  • Keep clear - do not touch the panels, rooftop isolators, DC cables or the inverter
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x2EFault
The frequency measured on L1 is higher than the thresholds

The frequency measured on L1 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x2FFault
The frequency measured on L2 is higher than the thresholds

The frequency measured on L2 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x30Fault
The frequency measured on L3 is higher than the thresholds

The frequency measured on L3 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x31Fault
The frequency measured on L1 is Lower than the thresholds

The frequency measured on L1 is Lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x32Fault
The frequency measured on L2 is Lower than the thresholds

The frequency measured on L2 is Lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x33Fault
The frequency measured on L3 is Lower than the thresholds

The frequency measured on L3 is Lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x34Fault
The SolarEdge system normally eliminates DC overvoltage errors

The SolarEdge system normally eliminates DC overvoltage errors.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x35Fault
The SolarEdge system normally eliminates DC overvoltage errors

The SolarEdge system normally eliminates DC overvoltage errors.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x36Fault
AC grid voltage malfunction

AC grid voltage malfunction.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x37Fault
The SolarEdge system normally eliminates DC overvoltage errors

The SolarEdge system normally eliminates DC overvoltage errors.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x38Fault
AC grid voltage malfunction

AC grid voltage malfunction. When AC voltage returns the inverter should restart after the reconnection time.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x39Critical
Ground faults may occur due to insufficient insulation to the ground

Ground faults may occur due to insufficient insulation to the ground.

What you can do

  • Keep clear - do not touch the panels, rooftop isolators, DC cables or the inverter
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x42Fault
Grid Voltage Spike

Grid Voltage Spike

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x43Fault
Grid Voltage Spike

Grid Voltage Spike

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x44Fault
Grid Voltage Spike

Grid Voltage Spike

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x45Fault
DC Voltage Spike

DC Voltage Spike

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x46Fault
DC Voltage Spike

DC Voltage Spike

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x47Fault
Over temperature

Over temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x48Fault
Under temperature

Under temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x4FFault
Wrong AC connection

Wrong AC connection

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x52Fault
VDC+/- capacitors banks unbalanced

VDC+/- capacitors banks unbalanced

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x53Fault
VNN error

VNN error

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x54Fault
Low power

Low power

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x56Fault
Power train error

Power train error

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x57Fault
Broken or unconnected temperature sensor

Broken or unconnected temperature sensor.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x58Critical
PV solar array is not properly isolated from ground earth

PV solar array is not properly isolated from ground earth.

What you can do

  • Keep clear - do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar to test the earthing

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x59Fault
Relay Test

Relay Test

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x5BCritical
RCD Test

RCD Test

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x5DFault
Test Iso Test

Test Iso Test

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x6AFault
Power off AC to the inverter

Power off AC to the inverter

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x6BFault
Power off AC to the inverter

Power off AC to the inverter

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x75Fault
Capacitor over voltage

Capacitor over voltage

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x76Fault
Capacitor over voltage

Capacitor over voltage

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x77Fault
Over temperature

Over temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x78Fault
Over temperature

Over temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x79Fault
Over temperature

Over temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7AFault
Over current

Over current

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7BFault
Over current

Over current

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7CFault
Over current

Over current

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7DFault
Driver Short

Driver Short

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7EFault
Driver Short

Driver Short

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x7FFault
Driver Short

Driver Short

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x80Fault
Balancer Fault

Balancer Fault

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x81Fault
RCD Over Current

RCD Over Current

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x82Fault
EVENT_NC_TZ

EVENT_NC_TZ

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x83Fault
Global Fault

Global Fault

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x87Fault
The frequency measured on L1 is higher than the thresholds

The frequency measured on L1 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x88Fault
The frequency measured on L2 is higher than the thresholds

The frequency measured on L2 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x89Fault
The frequency measured on L3 is higher than the thresholds

The frequency measured on L3 is higher than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x8AFault
The frequency measured on L1 is Lower than the thresholds

The frequency measured on L1 is Lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x8BFault
The frequency measured on L2 is lower than the thresholds

The frequency measured on L2 is lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter
8x8CFault
The frequency measured on L3 is lower than the thresholds

The frequency measured on L3 is lower than the thresholds

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

Commercial three-phase inverters · Guide only. All work must be done by a licensed electrician.

Commercial three-phase inverters Inverter

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

SolarEdge is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides

Get a quote Call