Solinteg error codes explained

What 31 Solinteg inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
Mains LostFault
Mains Lost

Grid power outage, AC switch or circuit is disconnected.

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Grid Voltage FaultFault
Grid Voltage Fault

Grid overvoltage or undervoltage: the grid voltage is higher or lower than the set protection value.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Grid Frequency FaultFault
Grid Frequency Fault

Grid over- or under-frequency: the grid frequency is higher or lower than the set protection value.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
DCI FaultFault
DCI Fault

DC injection high - the inverter detects a higher DC component in the AC output.

What you can do

  • Restart the system once using the owner shutdown/start-up steps in your manual
  • If it comes back, call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
ISO Over LimitationCritical
ISO Over Limitation

Low system insulation resistance, generally caused by poor insulation to ground of the modules/cables or a rainy, damp environment.

What you can do

  • Keep clear - do not touch the panels, rooftop isolators, DC cables or the inverter
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
GFCI FaultCritical
GFCI Fault

Excessive leakage current.

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
PV Over VoltageFault
PV Over Voltage

PV voltage is too high.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Bus Voltage FaultFault
Bus Voltage Fault

Internal DC bus voltage is too high.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Inverter Over TemperatureWarning
Inverter Over Temperature

The temperature inside the inverter is too high and out of the safe range.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
SPI FaultFault
SPI Fault

Internal communication failure (e.g. caused by a strong external magnetic field).

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
E2 FaultFault
E2 Fault

Internal storage (memory) anomaly (e.g. caused by a strong external magnetic field).

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
GFCI Device FaultFault
GFCI Device Fault

GFCI (leakage-current sensor) device anomaly.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
AC Transducer FaultFault
AC Transducer Fault

AC current sensor anomaly.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Relay Check FailFault
Relay Check Fail

Relay self-check failed - neutral and earth cables not connected well on the AC side, or an occasional failure.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Internal Fan FaultFault
Internal Fan Fault

Internal fan anomaly.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call your installer to arrange a fan check or replacement

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
External Fan FaultFault
External Fan Fault

External fan anomaly.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call your installer to arrange a fan check or replacement

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Bus Voltage Hard FaultFault
Bus Voltage Hard Fault

Internal DC bus voltage is too high (hardware protection).

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
PV Power LowFault
PV Power Low

Solar power is low.

What you can do

  • This is normal at dawn, dusk, in heavy cloud or when panels are shaded
  • No action needed if it clears once the sun is up
  • If it shows in full sun, call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Bat OVFault
Bat OV

Battery voltage is too high.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Backup OVFault
Backup OV

Backup output voltage is too high.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry
  • If it trips with only small loads on, or you suspect a short circuit, keep clear and call a licensed electrician

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Bus Volt LowFault
Bus Volt Low

Internal DC bus voltage is too low.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Hard FaultFault
Hard Fault

Other (hardware) faults.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Backup OPFault
Backup OP

Backup output overload.

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Inverter OVFault
Inverter OV

Backup output overvoltage.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry
  • If it trips with only small loads on, or you suspect a short circuit, keep clear and call a licensed electrician

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Inverter OFFault
Inverter OF

Backup output over-frequency.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry
  • If it trips with only small loads on, or you suspect a short circuit, keep clear and call a licensed electrician

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Inverter OCFault
Inverter OC

Backup output overcurrent.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry
  • If it trips with only small loads on, or you suspect a short circuit, keep clear and call a licensed electrician

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Phase Order ErrFault
Phase Order Err

Phase sequence error.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
SCI FaultFault
SCI Fault

Internal communication failure (e.g. caused by a strong external magnetic field).

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
FLASH FaultFault
FLASH Fault

Internal storage (flash) anomaly (e.g. caused by a strong external magnetic field).

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Meter Comm FaultFault
Meter Comm Fault

Inverter and meter communication abnormal.

What you can do

  • Check the monitoring app for the alarm and whether export/consumption readings look wrong
  • Restart your home router if the meter talks over Wi-Fi or LAN
  • Call your installer - meter and CT wiring is inside the switchboard and must be checked by a licensed electrician

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter
Battery FaultFault
Battery Fault

Battery fault.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear, call your installer, and call 000 if there is smoke

MHT-4~20K three-phase hybrid · Guide only. All work must be done by a licensed electrician.

MHT-4~20K three-phase hybrid Inverter

Common Solinteg questions

What does Solinteg Mains Lost "Mains Lost" mean?

Grid power outage, AC switch or circuit is disconnected. Check whether the rest of your house or street has power, and check your network operator's outage map This is a guide only; any electrical work must be done by a licensed electrician.

What does Solinteg Grid Voltage Fault "Grid Voltage Fault" mean?

Grid overvoltage or undervoltage: the grid voltage is higher or lower than the set protection value. This is usually caused by the mains supply, not the solar system This is a guide only; any electrical work must be done by a licensed electrician.

What does Solinteg Grid Frequency Fault "Grid Frequency Fault" mean?

Grid over- or under-frequency: the grid frequency is higher or lower than the set protection value. This is caused by the mains frequency moving outside the allowed range, usually briefly This is a guide only; any electrical work must be done by a licensed electrician.

What does Solinteg DCI Fault "DCI Fault" mean?

DC injection high - the inverter detects a higher DC component in the AC output. Restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does Solinteg PV Over Voltage "PV Over Voltage" mean?

PV voltage is too high. Do not touch the DC isolators or cables This is a guide only; any electrical work must be done by a licensed electrician.

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.