Solis error codes explained

What 66 Solis inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
OffFault
Off

Control device to shutdown

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByEPMFault
LmtByEPM

The device's output is under controlled

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByDRMFault
LmtByDRM

DRM Function ON

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByTempWarning
LmtByTemp

Over temperature power limited

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByFreqWarning
LmtByFreq

Frequency power limited

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByVgFault
LmtByVg

The device is in the Volt-Watt mode

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByVarFault
LmtByVar

The device is in the Volt-Var mode of operation

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
LmtByUnFrWarning
LmtByUnFr

Under frequency limit

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
StandbyFault
Standby

Bypass run

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
StandbySynochWarning
StandbySynoch

Off grid status to On grid status

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
GridToLoadFault
GridToLoad

Grid to load

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
Surge AlarmFault
Surge Alarm

On-site grid surge

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-V01Warning
OV-G-V01

Grid voltage exceeds the upper voltage range

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-G-V01Warning
UN-G-V01

Grid voltage exceeds the lower voltage range

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-F01Warning
OV-G-F01

Grid frequency exceeds the upper frequency range

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-G-F01Warning
UN-G-F01

Grid frequency exceeds the lower frequency range

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
G-PHASEWarning
G-PHASE

Unbalanced grid voltage

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
G-F-GLUWarning
G-F-GLU

Grid voltage frequency fluctuation

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
NO-GridInfo
NO-Grid

No grid

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-V02Warning
OV-G-V02

Grid transient overvoltage

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-V03Warning
OV-G-V03

Grid transient overvoltage

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
IGFOL-FFault
IGFOL-F

Grid current tracking failure

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-V05Warning
OV-G-V05

Grid voltage RMS instanta- neous overvoltage fault

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-V04Warning
OV-G-V04

Grid voltage exceeds the upper voltage range

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-G-V02Warning
UN-G-V02

Grid voltage exceeds the lower voltage range

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-F02Warning
OV-G-F02

Grid frequency exceeds the upper frequency range

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-G-F02Warning
UN-G-F02

Grid frequency exceeds the lower frequency range

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
NO-BatteryFault
NO-Battery

Battery is not connected

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-VbackupWarning
OV-Vbackup

Inverting overvoltage

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
Over-LoadWarning
Over-Load

Load overload fault

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
BatName-FAILFault
BatName-FAIL

Wrong battery brand selection

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
CAN FailFault
CAN Fail

CAN Fail

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-VbattFault
OV-Vbatt

Battery undervoltage detected

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-VbattFault
UN-Vbatt

Battery overvoltage detected

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
Fan AlarmWarning
Fan Alarm

Fan alarm

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-DC01 (1020 DATA:0001)Fault
OV-DC01 (1020 DATA:0001)

DC 1 input overvoltage

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-DC02 (1020 DATA:0002)Fault
OV-DC02 (1020 DATA:0002)

DC 2 input overvoltage

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-BUS (1021 DATA:0000)Fault
OV-BUS (1021 DATA:0000)

DC bus overvoltage

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-BUS01 (1023 DATA:0001)Fault
UN-BUS01 (1023 DATA:0001)

DC bus undervoltage

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UNB-BUS (1022 DATA:0000)Warning
UNB-BUS (1022 DATA:0000)

DC bus unbalanced voltage

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-BUS02 (1023 DATA:0002)Fault
UN-BUS02 (1023 DATA:0002)

Abnormal detection of DC bus voltage

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
DC-INTF. (1027 DATA:0000)Fault
DC-INTF. (1027 DATA:0000)

DC hardware overcurrent (1, 2, 3, 4)

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-G-I (1018 DATA:0000)Fault
OV-G-I (1018 DATA:0000)

A phase RMS value overcurrent

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-DCA-I (1025 DATA:0000)Fault
OV-DCA-I (1025 DATA:0000)

DC 1 average overcurrent

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-DCB-I (1026 DATA:0000)Fault
OV-DCB-I (1026 DATA:0000)

DC 2 average overcurrent

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
GRID-INTF. (1030 DATA:0000)Fault
GRID-INTF. (1030 DATA:0000)

AC hardware overcurrent (abc phase)

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
DCInj-FAULT (1037 DATA:0000)Fault
DCInj-FAULT (1037 DATA:0000)

The current DC component exceeds the limit

What you can do

  • Restart the system once using the owner shutdown/start-up steps in your manual
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
IGBT-OV-I (1048 DATA:0000)Fault
IGBT-OV-I (1048 DATA:0000)

IGBT overcurrent

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-TEM (1032 DATA:0000)Warning
OV-TEM (1032 DATA:0000)

Module over temperature

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
RelayChk-FAIL (1035 DATA:0000)Fault
RelayChk-FAIL (1035 DATA:0000)

Relay failure

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
UN-TEM (103A DATA:0000)Warning
UN-TEM (103A DATA:0000)

Low temperature protection

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
PV ISO-PRO01 (1033 DATA:0001)Safety-Critical
PV ISO-PRO01 (1033 DATA:0001)

PV negative ground fault

What you can do

  • Do not touch the panels, rooftop isolators or DC cables
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If it clears by itself once things dry out, still let us know if it keeps returning
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
PV ISO-PRO02 (1033 DATA:0002)Safety-Critical
PV ISO-PRO02 (1033 DATA:0002)

PV positive ground fault

What you can do

  • Do not touch the panels, rooftop isolators or DC cables
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If it clears by itself once things dry out, still let us know if it keeps returning
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
12Power-FAULT (1038 DATA:0000)Fault
12Power-FAULT (1038 DATA:0000)

12V undervoltage failure

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ILeak-PRO01 (1034 DATA:0001)Safety-Critical
ILeak-PRO01 (1034 DATA:0001)

Leakage current failure 01 (30mA)

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ILeak-PRO02 (1034 DATA:0002)Safety-Critical
ILeak-PRO02 (1034 DATA:0002)

Leakage current failure 02 (60mA)

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ILeak-PRO03 (1034 DATA:0003)Safety-Critical
ILeak-PRO03 (1034 DATA:0003)

Leakage current failure 03 (150mA)

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ILeak-PRO04 (1034 DATA:0004)Safety-Critical
ILeak-PRO04 (1034 DATA:0004)

Leakage current failure 04

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ILeak_Check (1039 DATA:0000)Safety-Critical
ILeak_Check (1039 DATA:0000)

Leakage current sensor failure

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
GRID-INTF02 (1046 DATA:0000)Fault
GRID-INTF02 (1046 DATA:0000)

Power grid disturbance 02

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-Vbatt-H/ OV-BUS-H (1051 DATA:0000)Fault
OV-Vbatt-H/ OV-BUS-H (1051 DATA:0000)

Battery overvoltage hardware failure / VBUS

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
OV-ILLC (1052 DATA:0000)Fault
OV-ILLC (1052 DATA:0000)

LLC hardware overcurrent

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
INI-FAULT (1031 DATA:0000)Fault
INI-FAULT (1031 DATA:0000)

AD zero drift overlink

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
DSP-B-FAULT (1036 DATA:0000)Warning
DSP-B-FAULT (1036 DATA:0000)

The master-slave DSP communication is abnormal

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
AFCI-Check (1040 DATA:0000)Safety-Critical
AFCI-Check (1040 DATA:0000)

AFCI self-test failure

What you can do

  • Keep clear of the inverter, panels and DC cables, and do not touch any isolators
  • Note the code, date and time, and check whether the alarm is still showing in the app
  • If you smell burning or see smoke, get everyone out and call 000
  • Call a licensed electrician or Total Solar - an arc fault means a DC wiring or connector problem that must be inspected

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter
ARC- FAULT (1041 DATA:0000)Safety-Critical
ARC- FAULT (1041 DATA:0000)

AFCI failure

What you can do

  • Keep clear of the inverter, panels and DC cables, and do not touch any isolators
  • Note the code, date and time, and check whether the alarm is still showing in the app
  • If you smell burning or see smoke, get everyone out and call 000
  • Call a licensed electrician or Total Solar - an arc fault means a DC wiring or connector problem that must be inspected

S6-EH3P(5-10)K-H-AU three-phase hybrid · Guide only. All work must be done by a licensed electrician.

S6-EH3P(5-10)K-H-AU three-phase hybrid Inverter

Common Solis questions

What does Solis Off "Off" mean?

Control device to shutdown Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does Solis LmtByEPM "LmtByEPM" mean?

The device's output is under controlled Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does Solis LmtByDRM "LmtByDRM" mean?

DRM Function ON Note the code, date and time and check the monitoring app This is a guide only; any electrical work must be done by a licensed electrician.

What does Solis LmtByVg "LmtByVg" mean?

The device is in the Volt-Watt mode Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

What does Solis LmtByVar "LmtByVar" mean?

The device is in the Volt-Var mode of operation Note the code, then restart the system once using the owner shutdown/start-up steps in your manual This is a guide only; any electrical work must be done by a licensed electrician.

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

Solis is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides

Get a quote Call