Steca error codes explained
What 41 Steca inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.
Safety first: never open the switchboard, remove covers, or pull apart or disconnect the inverter, batteries, isolators or wiring. Only use the switches and buttons described here. Anything else must be done by a licensed electrician. Call 1300 209 503 or book a service request.
| Code | Message & meaning |
|---|---|
| Boost converter defectiveFault |
Boost converter defectiveThe boost converter is defective, the inverter is not injecting into the grid or is injecting at reduced power. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Boost converter has wrong HW versionFault |
Boost converter has wrong HW versionThe inverter cannot identify an internal component, or it does not match the other components. The inverter cannot inject into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Boost converter malfunctionFault |
Boost converter malfunctionAn internal component of the inverter is defective. It is possible that the inverter injects into the grid not at all, or with reduced capacity. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Boost converter not connectedFault |
Boost converter not connectedThe connection of the internal components is interrupted. The inverter is not injecting into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Boost converter not recognisedFault |
Boost converter not recognisedBoost converter not recognised What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| CountryCode failedFault |
CountryCode failedThere is an inconsistency between the selected country setting and the country setting stored in memory. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Country parameters invalidFault |
Country parameters invalidThe inverter cannot inject into the grid because it has no valid parameters. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Device overheatedFault |
Device overheatedIn spite of capacity reduction, the maximum permissible temperature is exceeded. The inverter does not inject into the grid until the permissible temperature range is reached. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Data transfer failedFault |
Data transfer failedA setting failed, for example during initial commissioning, because it has not been properly adopted. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Fan faultyFault |
Fan faultyThe internal fan of the inverter is defective. It is possible that the inverter injects into the grid with reduced capacity. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| FE not connectedCritical |
FE not connectedThe protective earth is not connected. For safety reasons the inverter is not allowed to inject into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid current DC offset too highFault |
Grid current DC offset too highThe DC current power share that is injected by the inverter into the grid, exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid frequency too highFault |
Grid frequency too highThe grid frequency applied on the inverter exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid frequency too high for reactivationFault |
Grid frequency too high for reactivationAfter switch-off, the inverter cannot inject again because the grid voltage exceeds the legally prescribed switch-on value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid frequency too lowFault |
Grid frequency too lowThe grid frequency applied on the inverter is below the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid frequency too low reactivationFault |
Grid frequency too low reactivationAfter switch-off, the inverter cannot inject again because the grid voltage is below the legally prescribed switch-on value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid islanding detectedFault |
Grid islanding detectedThe grid is not carrying any voltage (self-run of the inverter). For safety reasons the inverter is not allowed to inject into the grid. It switches itself off as long as the error is present (display dark). What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid relay defectiveFault |
Grid relay defectiveThe inverter has detected that a grid relay is defective; for this reason, it is not injecting into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage too highFault |
Grid voltage too highThe grid voltage applied on the inverter exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage (average) too highFault |
Grid voltage (average) too highThe output voltage averaged over the legally prescribed time period exceeds the permissible tolerance range. The inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage too lowFault |
Grid voltage too lowThe grid voltage applied on the inverter is below the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage (average) too lowFault |
Grid voltage (average) too lowThe output voltage averaged over the legally prescribed time period is below the permissible tolerance range. The inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage too high for reactivationFault |
Grid voltage too high for reactivationAfter switching off, the inverter cannot resume feeding because the grid voltage exceeds the legally prescribed switch-on value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Grid voltage too low for reactivationFault |
Grid voltage too low for reactivationAfter switch-off, the inverter cannot inject again because the grid voltage is below the legally prescribed switch-on value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Intern.errorFault |
Intern.errorIntern.error What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Intern. infoInfo |
Intern. infoIntern. info What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Intern. warningWarning |
Intern. warningIntern. warning What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Isolation errorCritical |
Isolation errorThe insulating resistor between plus and minus input and ground underranges the permissible value. For safety reasons the inverter is not allowed to inject into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| L and N swappedCritical |
L and N swappedOuter conductor and neutral conductor are connected swapped out. For safety reasons the inverter is not allowed to inject into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| No brandingFault |
No brandingThe inverter has incorrect or faulty device data. For this reason, the inverter cannot inject into the grid. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| No connection to the energy meterFault |
No connection to the energy meterThe communication connection between the inverter and the energy meter does not exist or is defective. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Overtemperature HSSFault |
Overtemperature HSSThe maximum permissible boost converter temperature has been exceeded. The inverter does not inject into the grid until the permissible temperature range is reached. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Power reduction due to temperatureWarning |
Power reduction due to temperatureThe inverter reduces it output power because the maximum permissible temperature has been reached. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| PV current too highFault |
PV current too highThe input current at the inverter exceeds the permissible value. The inverter limits the current to the permissible value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| PV voltage too highFault |
PV voltage too highThe input voltage applied on the inverter exceeds the permissible value. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Reading CountryCode failedFault |
Reading CountryCode failedThe inverter could not correctly read out the country setting from the memory. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Residual current too highCritical |
Residual current too highThe fault current that flows from the plus or minus input via the PV generators exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| RS485 Gateway activatedFault |
RS485 Gateway activatedNo communication with the inverter possible via the RS485 interface. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Self test failedFault |
Self test failedAn error occurred during the self-test, the self-test has been aborted. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Software incompatibleFault |
Software incompatibleAfter a firmware update, the different software statuses in the inverter do not match any more. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
| Time/date lostWarning |
Time/date lostThe inverter lost the time because it remained unconnected from the grid for too long a time. Yield data cannot be stored, event messages only with incorrect date. What you can do
StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician. |
No codes match. Try fewer characters, or ask us.
Common Steca questions
What does Steca Boost converter defective "Boost converter defective" mean?
The boost converter is defective, the inverter is not injecting into the grid or is injecting at reduced power. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does Steca Boost converter has wrong HW version "Boost converter has wrong HW version" mean?
The inverter cannot identify an internal component, or it does not match the other components. The inverter cannot inject into the grid. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does Steca Boost converter malfunction "Boost converter malfunction" mean?
An internal component of the inverter is defective. It is possible that the inverter injects into the grid not at all, or with reduced capacity. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does Steca Boost converter not connected "Boost converter not connected" mean?
The connection of the internal components is interrupted. The inverter is not injecting into the grid. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does Steca Boost converter not recognised "Boost converter not recognised" mean?
Boost converter not recognised Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
Need help with this fault?
Get a licensed electrician to call you back.