Steca error codes explained

What 41 Steca inverter fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
Boost converter defectiveFault
Boost converter defective

The boost converter is defective, the inverter is not injecting into the grid or is injecting at reduced power.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Boost converter has wrong HW versionFault
Boost converter has wrong HW version

The inverter cannot identify an internal component, or it does not match the other components. The inverter cannot inject into the grid.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Boost converter malfunctionFault
Boost converter malfunction

An internal component of the inverter is defective. It is possible that the inverter injects into the grid not at all, or with reduced capacity.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Boost converter not connectedFault
Boost converter not connected

The connection of the internal components is interrupted. The inverter is not injecting into the grid.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Boost converter not recognisedFault
Boost converter not recognised

Boost converter not recognised

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
CountryCode failedFault
CountryCode failed

There is an inconsistency between the selected country setting and the country setting stored in memory.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Country parameters invalidFault
Country parameters invalid

The inverter cannot inject into the grid because it has no valid parameters.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Device overheatedFault
Device overheated

In spite of capacity reduction, the maximum permissible temperature is exceeded. The inverter does not inject into the grid until the permissible temperature range is reached.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Data transfer failedFault
Data transfer failed

A setting failed, for example during initial commissioning, because it has not been properly adopted.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Fan faultyFault
Fan faulty

The internal fan of the inverter is defective. It is possible that the inverter injects into the grid with reduced capacity.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call your installer to arrange a fan check or replacement

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
FE not connectedCritical
FE not connected

The protective earth is not connected. For safety reasons the inverter is not allowed to inject into the grid.

What you can do

  • Keep clear - do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar to test the earthing

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid current DC offset too highFault
Grid current DC offset too high

The DC current power share that is injected by the inverter into the grid, exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • Restart the system once using the owner shutdown/start-up steps in your manual
  • If it comes back, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid frequency too highFault
Grid frequency too high

The grid frequency applied on the inverter exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid frequency too high for reactivationFault
Grid frequency too high for reactivation

After switch-off, the inverter cannot inject again because the grid voltage exceeds the legally prescribed switch-on value.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid frequency too lowFault
Grid frequency too low

The grid frequency applied on the inverter is below the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid frequency too low reactivationFault
Grid frequency too low reactivation

After switch-off, the inverter cannot inject again because the grid voltage is below the legally prescribed switch-on value.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid islanding detectedFault
Grid islanding detected

The grid is not carrying any voltage (self-run of the inverter). For safety reasons the inverter is not allowed to inject into the grid. It switches itself off as long as the error is present (display dark).

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid relay defectiveFault
Grid relay defective

The inverter has detected that a grid relay is defective; for this reason, it is not injecting into the grid.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage too highFault
Grid voltage too high

The grid voltage applied on the inverter exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage (average) too highFault
Grid voltage (average) too high

The output voltage averaged over the legally prescribed time period exceeds the permissible tolerance range. The inverter switches off automatically as long as this fault is pending.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage too lowFault
Grid voltage too low

The grid voltage applied on the inverter is below the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage (average) too lowFault
Grid voltage (average) too low

The output voltage averaged over the legally prescribed time period is below the permissible tolerance range. The inverter switches off automatically as long as this fault is pending.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage too high for reactivationFault
Grid voltage too high for reactivation

After switching off, the inverter cannot resume feeding because the grid voltage exceeds the legally prescribed switch-on value.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Grid voltage too low for reactivationFault
Grid voltage too low for reactivation

After switch-off, the inverter cannot inject again because the grid voltage is below the legally prescribed switch-on value.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Intern.errorFault
Intern.error

Intern.error

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Intern. infoInfo
Intern. info

Intern. info

What you can do

  • No action needed - this is a status message, not a fault
  • If it stays for a long time or the system isn't producing when it should, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Intern. warningWarning
Intern. warning

Intern. warning

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Isolation errorCritical
Isolation error

The insulating resistor between plus and minus input and ground underranges the permissible value. For safety reasons the inverter is not allowed to inject into the grid.

What you can do

  • Keep clear - do not touch the panels, rooftop isolators, DC cables or the inverter
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
L and N swappedCritical
L and N swapped

Outer conductor and neutral conductor are connected swapped out. For safety reasons the inverter is not allowed to inject into the grid.

What you can do

  • Keep clear - do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar to test the earthing

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
No brandingFault
No branding

The inverter has incorrect or faulty device data. For this reason, the inverter cannot inject into the grid.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
No connection to the energy meterFault
No connection to the energy meter

The communication connection between the inverter and the energy meter does not exist or is defective.

What you can do

  • Check the monitoring app for the alarm and whether export/consumption readings look wrong
  • Restart your home router if the meter talks over Wi-Fi or LAN
  • Call your installer - meter and CT wiring is inside the switchboard and must be checked by a licensed electrician

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Overtemperature HSSFault
Overtemperature HSS

The maximum permissible boost converter temperature has been exceeded. The inverter does not inject into the grid until the permissible temperature range is reached.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Power reduction due to temperatureWarning
Power reduction due to temperature

The inverter reduces it output power because the maximum permissible temperature has been reached.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
PV current too highFault
PV current too high

The input current at the inverter exceeds the permissible value. The inverter limits the current to the permissible value.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
PV voltage too highFault
PV voltage too high

The input voltage applied on the inverter exceeds the permissible value.

What you can do

  • Do not touch the DC isolators or cables
  • Note the time - this often shows on cold, very sunny mornings
  • Call your installer - the panel strings may need to be checked against the inverter's limits

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Reading CountryCode failedFault
Reading CountryCode failed

The inverter could not correctly read out the country setting from the memory.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Residual current too highCritical
Residual current too high

The fault current that flows from the plus or minus input via the PV generators exceeds the permissible value. Pursuant to statutory regulations, the inverter switches off automatically as long as this fault is pending.

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • If you see smoke, smell burning or hear crackling, keep everyone away and call 000
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
RS485 Gateway activatedFault
RS485 Gateway activated

No communication with the inverter possible via the RS485 interface.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Self test failedFault
Self test failed

An error occurred during the self-test, the self-test has been aborted.

What you can do

  • Note the code, time and whether it clears by itself
  • You may restart the system once using the owner shutdown/start-up steps in your manual. Do not open covers or touch cabling
  • If the code returns or the system stays offline, call your installer - internal faults are a warranty/technician job

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Software incompatibleFault
Software incompatible

After a firmware update, the different software statuses in the inverter do not match any more.

What you can do

  • Make sure the system is online so it can receive updates
  • Restart the system once using the owner steps in your manual
  • If the alarm stays, call your installer - settings and firmware must be fixed by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter
Time/date lostWarning
Time/date lost

The inverter lost the time because it remained unconnected from the grid for too long a time. Yield data cannot be stored, event messages only with incorrect date.

What you can do

  • Don't change installer settings yourself
  • Call your installer - country/grid settings and configuration must be set by them or the manufacturer

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) · Guide only. All work must be done by a licensed electrician.

StecaGrid coolcept / coolcept-x (1500-4200, 3010-4200x) Inverter

Common Steca questions

What does Steca Boost converter defective "Boost converter defective" mean?

The boost converter is defective, the inverter is not injecting into the grid or is injecting at reduced power. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.

What does Steca Boost converter has wrong HW version "Boost converter has wrong HW version" mean?

The inverter cannot identify an internal component, or it does not match the other components. The inverter cannot inject into the grid. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.

What does Steca Boost converter malfunction "Boost converter malfunction" mean?

An internal component of the inverter is defective. It is possible that the inverter injects into the grid not at all, or with reduced capacity. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.

What does Steca Boost converter not connected "Boost converter not connected" mean?

The connection of the internal components is interrupted. The inverter is not injecting into the grid. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.

What does Steca Boost converter not recognised "Boost converter not recognised" mean?

Boost converter not recognised Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

Steca is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides

Get a quote Call