FoxESS H3/AC3 three-phase hybrid & AC-coupled error codes explained

What 63 FoxESS H3/AC3 three-phase hybrid & AC-coupled inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
Grid Lost FaultInfo
Grid Lost Fault

Grid is lost.

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Grid Volt FaultWarning
Grid Volt Fault

Grid voltage out of range.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Grid Freq FaultWarning
Grid Freq Fault

Grid frequency out of range.

What you can do

  • This is caused by the mains frequency moving outside the allowed range, usually briefly
  • The inverter reconnects by itself once the grid is stable
  • If it keeps happening, note the times and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
PLL_ OverTimeFault
PLL_ OverTime

Three-phase system access single-phase AC.

What you can do

  • Note the code, date and time and check the monitoring app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If it comes back, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
10min Volt FaultWarning
10min Volt Fault

The grid voltage is out of range for the last 10 Minutes.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
SW Inv Cur FaultWarning
SW Inv Cur Fault

Output current high detected by software. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above.

What you can do

  • Make sure the system is online so it can receive updates
  • Restart the system once using the owner steps in your manual
  • If the alarm stays, call your installer - settings and firmware must be fixed by them or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
DCI FaultFault
DCI Fault

DC component is out of limit in output current.

What you can do

  • Restart the system once using the owner shutdown/start-up steps in your manual
  • If it comes back, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
HW Inv Cur FaultFault
HW Inv Cur Fault

Output current high detected by hardware.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
SW Bus Vol FaultWarning
SW Bus Vol Fault

Bus voltage out of range detected by software. Please check whether the N line is connected to the GRID port of the inverter. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above.

What you can do

  • Make sure the system is online so it can receive updates
  • Restart the system once using the owner steps in your manual
  • If the alarm stays, call your installer - settings and firmware must be fixed by them or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Volt FaultFault
Bat Volt Fault

Battery voltage fault.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
SW Bat Cur FaultFault
SW Bat Cur Fault

Battery current high detected by software.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Iso FaultSafety-Critical
Iso Fault

The isolation is failed.

What you can do

  • Do not touch the panels, rooftop isolators or DC cables
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If it clears by itself once things dry out, still let us know if it keeps returning
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Res Cur FaultSafety-Critical
Res Cur Fault

The residual current is high.

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Pv Volt FaultFault
Pv Volt Fault

PV voltage out of range.

What you can do

  • Check solar generation in the app compared with similar days
  • Do not touch the DC isolators, cables or connectors, and don't go on the roof
  • If it doesn't clear by itself, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
SW Pv Cur FaultFault
SW Pv Cur Fault

PV input current high detected by software.

What you can do

  • Check solar generation in the app compared with similar days
  • Do not touch the DC isolators, cables or connectors, and don't go on the roof
  • If it doesn't clear by itself, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Temp FaultWarning
Temp Fault

The inverter temperature is high.

What you can do

  • Check from a safe distance that the inverter is shaded, has clear space around it and that nothing is blocking the vents
  • It usually recovers once it cools down
  • If it repeats often or you can hear a noisy/failed fan, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Ground FaultSafety-Critical
Ground Fault

The ground connection is failed.

What you can do

  • Do not touch the panels, rooftop isolators or DC cables
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If it clears by itself once things dry out, still let us know if it keeps returning
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Over Load FaultWarning
Over Load Fault

Over load in on grid mode.

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Eps Over LoadWarning
Eps Over Load

Over load in off grid mode.

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Power LowInfo
Bat Power Low

The battery power is low.

What you can do

  • This normally means the battery is low or has reached its reserve level
  • Let the system recharge from solar or the grid - check the state of charge in the app
  • If the battery never charges or stays at 0% for more than a day of sunshine, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
HW Bus Vol FaultFault
HW Bus Vol Fault

Bus voltage out of range detected by hardware.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
HW Pv Cur FaultFault
HW Pv Cur Fault

PV input current high detected by hardware. Check whether PV positive and negative are connected.

What you can do

  • Check solar generation in the app compared with similar days
  • Do not touch the DC isolators, cables or connectors, and don't go on the roof
  • If it doesn't clear by itself, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
HW Bat Cur FaultFault
HW Bat Cur Fault

Battery current high detected by hardware.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
SCI FaultWarning
SCI Fault

The communication between master and manager is fail.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
MDSP SPI FaultWarning
MDSP SPI Fault

The communication between master and slave is fail.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
MDSP Smpl FaultFault
MDSP Smpl Fault

The master sample detection circuit is failed.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Res Cur HW FaultSafety-Critical
Res Cur HW Fault

Residual current detection device is failed.

What you can do

  • Keep clear and do not touch the inverter or cabling
  • Note the code, date and time
  • Call a licensed electrician or Total Solar - this alarm means current may be leaking to earth

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Inv EEPROM FaultFault
Inv EEPROM Fault

The inverter eeprom is fault.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
PvCon Dir FaultFault
PvCon Dir Fault

The PV connection is reversed.

What you can do

  • Do not touch the DC isolators, cables or connectors
  • Call your installer - this points to a wiring problem that needs a licensed electrician

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Relay OpenFault
Bat Relay Open

The battery relay keeps open.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Relay Short CircuitFault
Bat Relay Short Circuit

The battery relay keeps close.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Buck FaultFault
Bat Buck Fault

The battery buck circuit mosfet is fail.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bat Boost FaultFault
Bat Boost Fault

The battery boost circuit mosfet is fail or The relay on the battery side of the inverter is not closed. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Eps Relay FaultWarning
Eps Relay Fault

The eps relay is failed.

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BatCon Dir FaultFault
BatCon Dir Fault

The battery connection is reversed.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Grid Relay FaultWarning
Grid Relay Fault

The grid relay keeps open or close.

What you can do

  • Turn off some large appliances (air-conditioners, ovens, kettles, pool pumps) - backup outputs have a power limit
  • The system usually recovers by itself once the load drops
  • If it keeps happening with normal loads, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
RDSP SPI FaultWarning
RDSP SPI Fault

The communication between master and slave is fail.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
RDSP Smpl FaultFault
RDSP Smpl Fault

The slave sample detection circuit is failed.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
ARM EEPROM FaultFault
ARM EEPROM Fault

The manager eeprom is fault.

What you can do

  • Note the code, then restart the system once using the owner shutdown/start-up steps in your manual
  • If the code comes back, call your installer - this is an internal fault that needs a licensed electrician or the manufacturer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Meter Lost FaultWarning
Meter Lost Fault

The communication between meter and inverter is interrupted.

What you can do

  • Check the monitoring app for the alarm and whether export/consumption readings look wrong
  • Restart your home router if the meter talks over Wi-Fi or LAN
  • Call your installer - meter and CT wiring is inside the switchboard and must be checked by a licensed electrician

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BMS LostFault
BMS Lost

The communication between BMS and inverter is interrupted.

What you can do

  • Check the app - the battery may show as offline or with no state of charge
  • Restart the system once using the shutdown and start-up steps in your owner's manual (battery last off, first on, unless your manual says otherwise)
  • If the alarm comes back, call your installer - battery communication cables must be checked by them

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Ext FaultFault
Bms Ext Fault

The communication between BMS and inverter is interrupted.

What you can do

  • Check the app - the battery may show as offline or with no state of charge
  • Restart the system once using the shutdown and start-up steps in your owner's manual (battery last off, first on, unless your manual says otherwise)
  • If the alarm comes back, call your installer - battery communication cables must be checked by them

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Int FaultFault
Bms Int Fault

DIP switch at the wrong position; The communication between battery packs is interrupted.

What you can do

  • Check the app - the battery may show as offline or with no state of charge
  • Restart the system once using the shutdown and start-up steps in your owner's manual (battery last off, first on, unless your manual says otherwise)
  • If the alarm comes back, call your installer - battery communication cables must be checked by them

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Volt HighFault
Bms Volt High

Battery over voltage.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Volt LowInfo
Bms Volt Low

Battery under voltage.

What you can do

  • This normally means the battery is low or has reached its reserve level
  • Let the system recharge from solar or the grid - check the state of charge in the app
  • If the battery never charges or stays at 0% for more than a day of sunshine, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms ChgCur HighFault
Bms ChgCur High

Battery charge over current.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms DchgCur HighFault
Bms DchgCur High

Battery discharge over current.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Temp HighSafety-Critical
Bms Temp High

Battery over temperature.

What you can do

  • Check from a safe distance for heat, swelling, hissing, a burning smell or smoke - if you notice any, keep everyone away and call 000
  • If nothing looks wrong, make sure the battery area is shaded and ventilated and nothing is stacked against it
  • Let the battery cool; most units recover by themselves
  • If the alarm keeps returning, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Temp LowSafety-Critical
Bms Temp Low

Battery under temperature.

What you can do

  • Check from a safe distance for heat, swelling, hissing, a burning smell or smoke - if you notice any, keep everyone away and call 000
  • If nothing looks wrong, make sure the battery area is shaded and ventilated and nothing is stacked against it
  • Let the battery cool; most units recover by themselves
  • If the alarm keeps returning, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BmsCellImbalanceWarning
BmsCellImbalance

The capacities of cells are different.

What you can do

  • This is usually caused by the mains supply, not the solar system
  • The inverter normally reconnects by itself once grid voltage is back in range
  • If it happens often (especially on sunny afternoons), note the times and call your installer - they can check the voltage and settings and talk to the network if needed

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms HW ProtectFault
Bms HW Protect

Battery hardware under protection.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BmsCircuit FaultWarning
BmsCircuit Fault

Bms hardware circuit fault.

What you can do

  • Check that your home Wi-Fi/internet is working and restart your router
  • Wait an hour - monitoring often reconnects by itself
  • If the inverter screen also shows a fault, or the alarm stays for more than a day, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Insul FaultSafety-Critical
Bms Insul Fault

Battery insulation fault.

What you can do

  • Do not touch the panels, rooftop isolators or DC cables
  • Note the code and whether it appears in wet weather or early morning - this helps the electrician
  • If it clears by itself once things dry out, still let us know if it keeps returning
  • Call a licensed electrician or Total Solar - insulation and earth faults need testing with proper equipment

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BmsVoltsSen FaultFault
BmsVoltsSen Fault

Battery voltage sensor fault.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BmsTempSen FaultSafety-Critical
BmsTempSen Fault

Battery temperature sensor fault.

What you can do

  • Check from a safe distance for heat, swelling, hissing, a burning smell or smoke - if you notice any, keep everyone away and call 000
  • If nothing looks wrong, make sure the battery area is shaded and ventilated and nothing is stacked against it
  • Let the battery cool; most units recover by themselves
  • If the alarm keeps returning, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
BmsCurSen FaultFault
BmsCurSen Fault

Battery current sensor fault.

What you can do

  • Turn off any very large loads that were running when the alarm appeared
  • Wait - many over-current protections reset automatically
  • If it keeps happening, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Relay FaultFault
Bms Relay Fault

Battery relay fault.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Type UnmatchFault
Bms Type Unmatch

The capacity of battery packs is different.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Ver UnmatchFault
Bms Ver Unmatch

The software between slaves are different.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms Mfg UnmatchFault
Bms Mfg Unmatch

The cell manufacture is different.

What you can do

  • Note the code and the battery state of charge shown in the app
  • Let the system run - some battery voltage protections clear by themselves after charging or discharging
  • If the alarm stays or keeps returning, call your installer - don't open or disconnect the battery yourself

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms SwHw UnmatchFault
Bms SwHw Unmatch

The slave software and hardware are not match.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms M&S UnmatchFault
Bms M&S Unmatch

The software between Master and Slave are not match.

What you can do

  • Check the battery status and any extra alarms in the app
  • Restart the system once using the owner shutdown/start-up steps in your manual if it allows
  • If the alarm comes back, or the battery is hot, swollen, noisy or smells, keep clear and call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter
Bms ChgReq NoAckInfo
Bms ChgReq NoAck

No action for charging request.

What you can do

  • Check whether the rest of your house or street has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar/inverter breaker - reset it once only; if it trips again, leave it off and call an electrician
  • Once normal power is back the inverter usually reconnects on its own within a few minutes
  • If the power is normal but the alarm stays, call your installer

H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician.

H3/AC3 three-phase hybrid & AC-coupled Inverter

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

FoxESS is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides

Get a quote Call