FoxESS error codes explained
What 396 FoxESS inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.
Safety first: never open the switchboard, remove covers, or pull apart or disconnect the inverter, batteries, isolators or wiring. Only use the switches and buttons described here. Anything else must be done by a licensed electrician. Call 1300 209 503 or book a service request.
Model guides: FoxESS H3-Plus / P3-Plus three-phase hybrid (AU) · FoxESS H3/AC3 three-phase hybrid & AC-coupled · FoxESS H1(G2)/AC1(G2) hybrid & AC-coupled (AU)
| Code | Message & meaning |
|---|---|
| Grid Lost FaultWarning |
Grid is lostThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Grid Volt FaultWarning |
Grid voltage out of rangeThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Grid Freq FaultWarning |
Grid frequency out of rangeGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| 10min Volt FaultWarning |
10-minute average grid voltage out of rangeThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| SW Inv Cur FaultFault |
Output current high (software)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| DCI FaultFault |
DC component in output current out of limitThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| HW Inv Cur FaultFault |
Output current high (hardware)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| SW Bus Vol FaultFault |
Bus voltage out of range (software)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Volt FaultFault |
Battery voltage faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| SW Bat Cur FaultFault |
Battery current high (software)The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Iso FaultCritical |
Isolation (insulation) failedThe inverter's insulation check failed. FoxESS states this is how the earth fault alarm (IEC 62109-2 cl. 13.9) appears on this model: the screen shows the isolation fault and the red LED lights. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Res Cur FaultCritical |
Residual current highThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Pv Volt FaultFault |
PV voltage out of rangeThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| SW Pv Cur FaultFault |
PV input current high (software)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Temp FaultWarning |
Inverter temperature highThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Ground FaultCritical |
Ground connection failedThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Over Load FaultWarning |
Overload in on-grid modeThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Eps Over LoadWarning |
Overload in off-grid (EPS) modeThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Power LowInfo |
Battery power lowThe battery's state of charge or voltage is low, so the system has stopped discharging it to protect the cells. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| HW Bus Vol FaultFault |
Bus voltage out of range (hardware)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| HW Pv Cur FaultFault |
PV input current high (hardware)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| HW Bat Cur FaultFault |
Battery current high (hardware)The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| SCI FaultFault |
Master-manager communication failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| MDSP SPI FaultFault |
Master-slave communication failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| MDSP Smpl FaultFault |
Master sample detection circuit failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Res Cur HW FaultFault |
Residual current detection device failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Inv EEPROM FaultFault |
Inverter EEPROM faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| PvCon Dir FaultFault |
PV connection reversedA solar string or the battery appears to be connected with positive and negative swapped. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Relay OpenFault |
Battery relay stays openThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Relay Short CircuitFault |
Battery relay stays closedThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Buck FaultFault |
Battery buck circuit MOSFET failedThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Bat Boost FaultFault |
Battery boost circuit MOSFET failedThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Eps Relay FaultFault |
EPS relay failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| BatCon Dir FaultFault |
Battery connection reversedA solar string or the battery appears to be connected with positive and negative swapped. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Main Relay OpenFault |
Grid relay stays openThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| S1 Close FaultFault |
Grid relay S1 stays closedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| S2 Close FaultFault |
Grid relay S2 stays closedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| M1 Close FaultFault |
Grid relay M1 stays closedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| M2 Close FaultFault |
Grid relay M2 stays closedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| GridV Cons FaultFault |
Grid voltage sample mismatch (master/slave)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| GridF Cons FaultFault |
Grid frequency sample mismatch (master/slave)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Dci Cons FaultFault |
DCI sample mismatch (master/slave)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Rc Cons FaultFault |
Residual current sample mismatch (master/slave)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| RDSP SPI FaultFault |
Master-slave communication failed (RDSP)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| RDSP Smpl FaultFault |
Slave sample detection circuit failedThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| ARM EEPROM FaultFault |
Manager EEPROM faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| Meter Lost FaultWarning |
Meter communication interruptedThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled (AU) · Guide only. All work must be done by a licensed electrician. |
| BMS LostFault |
BMS communication interruptedThe inverter and battery (or parts inside the battery) have stopped talking to each other, so the battery may stop charging or discharging. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Ext FaultFault |
BMS external communication interruptedThe inverter and battery (or parts inside the battery) have stopped talking to each other, so the battery may stop charging or discharging. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Int FaultFault |
Communication between battery packs interrupted (or DIP switch wrong)The inverter and battery (or parts inside the battery) have stopped talking to each other, so the battery may stop charging or discharging. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Volt HighFault |
Battery over-voltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Volt LowFault |
Battery under-voltageThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS ChgCur HighFault |
Battery charge over-currentThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS DchgCur HighFault |
Battery discharge over-currentThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Temp HighCritical |
Battery over-temperatureThe battery (or one of its internal parts) is above its safe temperature, so charging or discharging is limited or stopped to protect it. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Temp LowWarning |
Battery under-temperatureThe battery is too cold to charge or discharge safely, so it is pausing until it warms up. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS CellImbalanceFault |
Cell capacity imbalanceThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS HW ProtectFault |
Battery hardware protectionThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Circuit FaultFault |
BMS hardware circuit faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Insul FaultCritical |
Battery insulation faultThe inverter measured low insulation resistance between the solar/battery DC circuits and earth. In Australia this is treated as an earth fault alarm, and the system must be checked by a licensed electrician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS VoltsSen FaultFault |
Battery voltage sensor faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS TempSen FaultFault |
Battery temperature sensor faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS CurSen FaultFault |
Battery current sensor faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Relay FaultFault |
Battery relay faultThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Type UnmatchFault |
Battery pack capacities differThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Ver UnmatchFault |
Battery slave software versions differThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS Mfg UnmatchFault |
Cell manufacturer differsThe battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS SwHw UnmatchFault |
Slave software/hardware mismatchThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS M&S UnmatchFault |
Master/slave software mismatchThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| BMS ChgReq NoAckFault |
No response to charge requestThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
H1(G2)/AC1(G2) hybrid & AC-coupled — battery (BMS) alarms · Guide only. All work must be done by a licensed electrician. |
| 1030Fault |
AC OvercurrentAC Overcurrent What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1034Fault |
DC Component Current FaultDC Component Current Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1035Safety-Critical |
High Leakage Current FaultHigh Leakage Current Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1036Safety-Critical |
Static Leakage Current FaultStatic Leakage Current Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1040Warning |
Unbalanced Grid VoltageUnbalanced Grid Voltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1042Warning |
Grid Frequency HighGrid Frequency High What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1043Warning |
Grid Frequency LowGrid Frequency Low What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1044Warning |
Grid Phase Voltage Over LimitGrid Phase Voltage Over Limit What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1045Warning |
Grid Line Voltage Over LimitGrid Line Voltage Over Limit What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1046Warning |
Unbalanced Inverter CurrentUnbalanced Inverter Current What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1048Warning |
High DC Component Voltage When Off-gridHigh DC Component Voltage When Off-grid What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1050Fault |
Inverter Hardware OvercurrentInverter Hardware Overcurrent What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1051Fault |
Grid Phase Drop FaultGrid Phase Drop Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1057Fault |
Bus Transient OvervoltageBus Transient Overvoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1070Fault |
Bus Differential High FaultBus Differential High Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1071Fault |
Bus Hardware OvervoltageBus Hardware Overvoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1084Warning |
Balancing Bridge Hardware OvercurrentBalancing Bridge Hardware Overcurrent What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1085Fault |
DC Input MPPT1 Access FaultDC Input MPPT1 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1086Fault |
DC Input MPPT2 Access FaultDC Input MPPT2 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1088Fault |
DC Input MPPT3 Access FaultDC Input MPPT3 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1091Warning |
Off grid command conflictOff grid command conflict What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1092Fault |
INV Relay FaultINV Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1093Warning |
EPS Relay FaultEPS Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1095Fault |
ESTOP TriggerESTOP Trigger What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1099Warning |
Overtemperature ProtectionOvertemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1102Fault |
Inverter Current DC Component Offset FaultInverter Current DC Component Offset Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1103Fault |
Inverter Current Offset FaultInverter Current Offset Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1106Fault |
Inverter Soft Start Timeout FaultInverter Soft Start Timeout Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1107Fault |
BUS Soft Start FaultBUS Soft Start Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1108Warning |
Abnormal Frequency Detection ValueAbnormal Frequency Detection Value What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1109Safety-Critical |
Leak Current CT Self-checking FaultLeak Current CT Self-checking Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1112Fault |
Internal Control Diagnosis FaultInternal Control Diagnosis Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1115Warning |
Balancing Bridge Current Sampling Channel FaultBalancing Bridge Current Sampling Channel Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1116Safety-Critical |
Ground Impedance FaultGround Impedance Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1123Fault |
Grid Relay FaultGrid Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1124Safety-Critical |
Low Insulation Impedance FaultLow Insulation Impedance Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1125Safety-Critical |
Ground Relay FaultGround Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1129Fault |
INV Open-loop Self-checking faultINV Open-loop Self-checking fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1132Warning |
INV Frequency Fault Under Off-gridINV Frequency Fault Under Off-grid What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1136Warning |
Load Overpower FaultLoad Overpower Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1137Warning |
INV Low Voltage Fault Under Off-gridINV Low Voltage Fault Under Off-grid What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1138Warning |
Redundant Detection Fault of Grid Voltage for Auxiliary DSPRedundant Detection Fault of Grid Voltage for Auxiliary DSP What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1139Warning |
Redundant Detection Fault of Grid Frequency for Auxiliary DSPRedundant Detection Fault of Grid Frequency for Auxiliary DSP What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1141Safety-Critical |
Redundant Detection Fault of Leak Current for Auxiliary DSPRedundant Detection Fault of Leak Current for Auxiliary DSP What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1145Safety-Critical |
Arc FaultArc Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1149Warning |
INV High Voltage Fault Under Off-gridINV High Voltage Fault Under Off-grid What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1154Fault |
INV Overcurrent Permanent FaultINV Overcurrent Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1157Fault |
Relay Permanent FaultRelay Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1160Fault |
INV SelfCheck Permanent FaultINV SelfCheck Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1163Warning |
Balancing Bridge Overcurrent Permanent FaultBalancing Bridge Overcurrent Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1173Fault |
Internal Control Diagnosis Permanent FaultInternal Control Diagnosis Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1174Fault |
BUS Hardware Overvoltage Permanent FaultBUS Hardware Overvoltage Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1176Fault |
BST Hardware Overcurrent Permanent FaultBST Hardware Overcurrent Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1177Safety-Critical |
Static Leak Current Permanent FaultStatic Leak Current Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1178Fault |
BUS Overvoltage Permanent FaultBUS Overvoltage Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1179Warning |
High BUS Voltage Imbalance Permanent FaultHigh BUS Voltage Imbalance Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1181Safety-Critical |
Arc Permanent FaultArc Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1182Fault |
BDC Overcurrent Permanent FaultBDC Overcurrent Permanent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1185Warning |
Abnormal Grid Startup VoltageAbnormal Grid Startup Voltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1186Warning |
Off-grid Running AlarmOff-grid Running Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1188Fault |
AC Lightening Protector AnomalyAC Lightening Protector Anomaly What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1189Fault |
DC Lightening Protector AnomalyDC Lightening Protector Anomaly What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1190Warning |
Temperature Sensor AlarmTemperature Sensor Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1191Warning |
External Fan AlarmExternal Fan Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1192Warning |
Internal Fan AlarmInternal Fan Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1193Fault |
EEPROM Write-read AlarmEEPROM Write-read Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1194Warning |
Slave to Master Communication AlarmSlave to Master Communication Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1195Fault |
Grid Phase Change AlarmGrid Phase Change Alarm What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1220Fault |
BDC Over Current FaultBDC Over Current Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1223Fault |
BDC Hardware Overcurrent FaultBDC Hardware Overcurrent Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1224Fault |
BDC3 Current Sampling Channel FaultBDC3 Current Sampling Channel Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1229Fault |
BDC Overtemperature FaultBDC Overtemperature Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1237Fault |
BDC1 Current SamplingBDC1 Current Sampling What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1238Fault |
BDC2 Current Sampling Channel FaultBDC2 Current Sampling Channel Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1241Fault |
BDC Soft Start FaultBDC Soft Start Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1243Fault |
BDC transient Overvoltage FaultBDC transient Overvoltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1244Fault |
BDC Average Overvoltage FaultBDC Average Overvoltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1249Warning |
External Communication ErrorExternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1250Warning |
Internal Communication ErrorInternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1251Fault |
Overvoltage ProtectionOvervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1252Fault |
Undervoltage ProtectionUndervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1253Fault |
Charging Overcurrent ProtectionCharging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1254Fault |
Discharging Overcurrent ProtectionDischarging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1255Safety-Critical |
Cell Overtemperature ProtectionCell Overtemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1256Safety-Critical |
Cell Undertemperature ProtectionCell Undertemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1257Warning |
BMS Cell ImbalanceBMS Cell Imbalance What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1258Fault |
Hardware ProtectionHardware Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1259Fault |
Circuit FaultCircuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1261Fault |
Voltage Sensor FaultVoltage Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1262Warning |
Temperature Sensor FaultTemperature Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1263Fault |
Current Sensor FaultCurrent Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1264Fault |
Relay FaultRelay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1281Warning |
Communication Fault between Communication Board and Main DSPCommunication Fault between Communication Board and Main DSP What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1282Warning |
Communication Fault between Communication Board and Auxiliary DSPCommunication Fault between Communication Board and Auxiliary DSP What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1283Fault |
Communication Fault between Communication Board and BMSCommunication Fault between Communication Board and BMS What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1284Warning |
Communication Fault between Communication Board and Built-in MeterCommunication Fault between Communication Board and Built-in Meter What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1285Warning |
Communication Fault between Communication Board and Grid MeterCommunication Fault between Communication Board and Grid Meter What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1286Warning |
Communication Board Flash Writing FaultCommunication Board Flash Writing Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1287Fault |
RTC Read-Write FaultRTC Read-Write Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1288Warning |
Communication Fault between Communication Board and HUB BoardCommunication Fault between Communication Board and HUB Board What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1289Warning |
Solar Meter Communication FaultSolar Meter Communication Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1290Warning |
GEN Meter Communication FaultGEN Meter Communication Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1291Warning |
Communication Fault between the Master and slaveCommunication Fault between the Master and slave What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1292Warning |
Meter's CT line faultMeter's CT line fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1293Warning |
Meter's Voltage line faultMeter's Voltage line fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1294Safety-Critical |
AFCI fault lock deviceAFCI fault lock device What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1295Fault |
Communication Fault between Communication Board and BMSCommunication Fault between Communication Board and BMS What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1296Fault |
Communication Fault between Communication Board and BMSCommunication Fault between Communication Board and BMS What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1313Fault |
Mppt1 High Voltage FaultMppt1 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1314Fault |
Mppt2 High Voltage FaultMppt2 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1315Fault |
Mppt3 High Voltage FaultMppt3 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1316Fault |
Mppt4 High Voltage FaultMppt4 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1317Fault |
Mppt5 High Voltage FaultMppt5 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1318Fault |
Mppt6 High Voltage FaultMppt6 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1319Fault |
Mppt7 High Voltage FaultMppt7 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1320Fault |
Mppt8 High Voltage FaultMppt8 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1321Fault |
Mppt9 High Voltage FaultMppt9 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1322Fault |
Mppt10 High Voltage FaultMppt10 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1323Fault |
Mppt11 High Voltage FaultMppt11 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1324Fault |
Mppt12 High Voltage FaultMppt12 High Voltage Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1325Fault |
DC Input MPPT4 Access FaultDC Input MPPT4 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1326Fault |
DC Input MPPT5 Access FaultDC Input MPPT5 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1327Fault |
DC Input MPPT6 Access FaultDC Input MPPT6 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1328Fault |
DC Input MPPT7 Access FaultDC Input MPPT7 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1329Fault |
DC Input MPPT8 Access FaultDC Input MPPT8 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1330Fault |
DC Input MPPT9 Access FaultDC Input MPPT9 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1331Fault |
DC Input MPPT10 Access FaultDC Input MPPT10 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1332Fault |
DC Input MPPT11 Access FaultDC Input MPPT11 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1333Fault |
DC Input MPPT12 Access FaultDC Input MPPT12 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1345Fault |
String1 Access FaultString1 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1346Fault |
String2 Access FaultString2 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1347Fault |
String3 Access FaultString3 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1348Fault |
String4 Access FaultString4 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1349Fault |
String5 Access FaultString5 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1350Fault |
String6 Access FaultString6 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1351Fault |
String7 Access FaultString7 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1352Fault |
String8 Access FaultString8 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1353Fault |
String9 Access FaultString9 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1354Fault |
String10 Access FaultString10 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1355Fault |
String11 Access FaultString11 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1356Fault |
String12 Access FaultString12 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1357Fault |
String13 Access FaultString13 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1358Fault |
String14 Access FaultString14 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1359Fault |
String15 Access FaultString15 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1360Fault |
String16 Access FaultString16 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1361Fault |
String17 Access FaultString17 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1362Fault |
String18 Access FaultString18 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1363Fault |
String19 Access FaultString19 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1364Fault |
String20 Access FaultString20 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1365Fault |
String21 Access FaultString21 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1366Fault |
String22 Access FaultString22 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1367Fault |
String23 Access FaultString23 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1368Fault |
String24 Access FaultString24 Access Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1409Warning |
HUB Grid OvervoltageHUB Grid Overvoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1410Warning |
HUB Grid UndervoltageHUB Grid Undervoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1411Warning |
HUB Grid Voltage OverfrequencyHUB Grid Voltage Overfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1412Warning |
HUB Grid Voltage UnderfrequencyHUB Grid Voltage Underfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1413Fault |
HUB Generator OvervoltageHUB Generator Overvoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1414Fault |
HUB Generator UndervoltageHUB Generator Undervoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1415Warning |
HUB Generator Voltage OverfrequencyHUB Generator Voltage Overfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1416Warning |
HUB Generator Voltage UnderfrequencyHUB Generator Voltage Underfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1417Fault |
HUB Load OvervoltageHUB Load Overvoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1418Fault |
HUB Load UndervoltageHUB Load Undervoltage What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1419Warning |
HUB Load Voltage OverfrequencyHUB Load Voltage Overfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1420Warning |
HUB Load Voltage UnderfrequencyHUB Load Voltage Underfrequency What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1421Warning |
HUB Grid Relay Short Circuit FaultHUB Grid Relay Short Circuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1422Fault |
HUB Grid Relay Open Circuit FaultHUB Grid Relay Open Circuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1423Warning |
HUB Generator Relay Short Circuit FaultHUB Generator Relay Short Circuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1424Fault |
HUB Generator Relay Open Circuit FaultHUB Generator Relay Open Circuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1425Fault |
HUB Load Voltage Anomaly FaultHUB Load Voltage Anomaly Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1426Warning |
HUB and Inverter Communication FaultHUB and Inverter Communication Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1427Warning |
HUB Overload FaultHUB Overload Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1428Fault |
Inconsistent Settings of Paralleled Inverters in HUB ModeInconsistent Settings of Paralleled Inverters in HUB Mode What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1429Warning |
HUB OvertemperatureHUB Overtemperature What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1430Fault |
Inconsistent Number of 485 and CAN CommunicationsInconsistent Number of 485 and CAN Communications What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1441Fault |
BDC1 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode)BDC1 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode) What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1442Fault |
BDC2 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode)BDC2 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode) What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1443Fault |
BDC3 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode)BDC3 Average Low Voltage Fault (Total battery voltage is below undervoltage value in non-charging mode) What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1444Fault |
BDC1 Pre-charging Resistor FaultBDC1 Pre-charging Resistor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1445Fault |
BDC2 Pre-charging Resistor FaultBDC2 Pre-charging Resistor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1446Fault |
BDC3 Pre-charging Resistor FaultBDC3 Pre-charging Resistor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1447Fault |
Reversed Battery1 Polarity Connection FaultReversed Battery1 Polarity Connection Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1448Fault |
Reversed Battery2 Polarity Connection FaultReversed Battery2 Polarity Connection Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1449Fault |
Reversed Battery3 Polarity Connection FaultReversed Battery3 Polarity Connection Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1450Fault |
Battery1 Pre-charging Relay FaultBattery1 Pre-charging Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1451Fault |
Battery2 Pre-charging Relay FaultBattery2 Pre-charging Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1452Fault |
Battery3 Pre-charging Relay FaultBattery3 Pre-charging Relay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1456Fault |
BDC1 Self-checking FaultBDC1 Self-checking Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1457Fault |
BDC2 Self-checking FaultBDC2 Self-checking Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1458Fault |
BDC3 Self-checking FaultBDC3 Self-checking Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1459Fault |
Battery1 Input FaultBattery1 Input Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1460Fault |
Battery2 Input FaultBattery2 Input Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1461Fault |
Battery3 Input FaultBattery3 Input Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1473Warning |
External Communication ErrorExternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1474Warning |
Internal Communication ErrorInternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1475Fault |
Overvoltage ProtectionOvervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1476Fault |
Undervoltage ProtectionUndervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1477Fault |
Charging Overcurrent ProtectionCharging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1478Fault |
Discharging Overcurrent ProtectionDischarging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1479Safety-Critical |
Cell Overtemperature ProtectionCell Overtemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1480Safety-Critical |
Cell Undertemperature ProtectionCell Undertemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1481Warning |
BMS Cell ImbalanceBMS Cell Imbalance What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1482Fault |
Hardware ProtectionHardware Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1483Fault |
Circuit FaultCircuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1485Fault |
Voltage Sensor FaultVoltage Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1486Warning |
Temperature Sensor FaultTemperature Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1487Fault |
Current Sensor FaultCurrent Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1488Fault |
Relay FaultRelay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1505Warning |
External Communication ErrorExternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1506Warning |
Internal Communication ErrorInternal Communication Error What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1507Fault |
Overvoltage ProtectionOvervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1508Fault |
Undervoltage ProtectionUndervoltage Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1509Fault |
Charging Overcurrent ProtectionCharging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1510Fault |
Discharging Overcurrent ProtectionDischarging Overcurrent Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1511Safety-Critical |
Cell Overtemperature ProtectionCell Overtemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1512Safety-Critical |
Cell Undertemperature ProtectionCell Undertemperature Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1513Warning |
BMS Cell ImbalanceBMS Cell Imbalance What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1514Fault |
Hardware ProtectionHardware Protection What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1515Fault |
Circuit FaultCircuit Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1517Fault |
Voltage Sensor FaultVoltage Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1518Warning |
Temperature Sensor FaultTemperature Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1519Fault |
Current Sensor FaultCurrent Sensor Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| 1520Fault |
Relay FaultRelay Fault What you can do
H3-Plus / P3-Plus three-phase hybrid (AU) · Guide only. All work must be done by a licensed electrician. |
| Grid Lost FaultInfo |
Grid Lost FaultGrid is lost. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Volt FaultWarning |
Grid Volt FaultGrid voltage out of range. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Freq FaultWarning |
Grid Freq FaultGrid frequency out of range. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| PLL_ OverTimeFault |
PLL_ OverTimeThree-phase system access single-phase AC. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| 10min Volt FaultWarning |
10min Volt FaultThe grid voltage is out of range for the last 10 Minutes. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Inv Cur FaultWarning |
SW Inv Cur FaultOutput current high detected by software. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| DCI FaultFault |
DCI FaultDC component is out of limit in output current. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| HW Inv Cur FaultFault |
HW Inv Cur FaultOutput current high detected by hardware. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Bus Vol FaultWarning |
SW Bus Vol FaultBus voltage out of range detected by software. Please check whether the N line is connected to the GRID port of the inverter. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Volt FaultFault |
Bat Volt FaultBattery voltage fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Bat Cur FaultFault |
SW Bat Cur FaultBattery current high detected by software. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Iso FaultSafety-Critical |
Iso FaultThe isolation is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Res Cur FaultSafety-Critical |
Res Cur FaultThe residual current is high. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Pv Volt FaultFault |
Pv Volt FaultPV voltage out of range. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Pv Cur FaultFault |
SW Pv Cur FaultPV input current high detected by software. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Temp FaultWarning |
Temp FaultThe inverter temperature is high. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Ground FaultSafety-Critical |
Ground FaultThe ground connection is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Over Load FaultWarning |
Over Load FaultOver load in on grid mode. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Eps Over LoadWarning |
Eps Over LoadOver load in off grid mode. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Power LowInfo |
Bat Power LowThe battery power is low. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| HW Bus Vol FaultFault |
HW Bus Vol FaultBus voltage out of range detected by hardware. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| HW Pv Cur FaultFault |
HW Pv Cur FaultPV input current high detected by hardware. Check whether PV positive and negative are connected. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| HW Bat Cur FaultFault |
HW Bat Cur FaultBattery current high detected by hardware. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SCI FaultWarning |
SCI FaultThe communication between master and manager is fail. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| MDSP SPI FaultWarning |
MDSP SPI FaultThe communication between master and slave is fail. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| MDSP Smpl FaultFault |
MDSP Smpl FaultThe master sample detection circuit is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Res Cur HW FaultSafety-Critical |
Res Cur HW FaultResidual current detection device is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Inv EEPROM FaultFault |
Inv EEPROM FaultThe inverter eeprom is fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| PvCon Dir FaultFault |
PvCon Dir FaultThe PV connection is reversed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Relay OpenFault |
Bat Relay OpenThe battery relay keeps open. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Relay Short CircuitFault |
Bat Relay Short CircuitThe battery relay keeps close. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Buck FaultFault |
Bat Buck FaultThe battery buck circuit mosfet is fail. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Boost FaultFault |
Bat Boost FaultThe battery boost circuit mosfet is fail or The relay on the battery side of the inverter is not closed. To upgrade to the latest software, at least ensure that the master is upgraded to 1.69 or above. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Eps Relay FaultWarning |
Eps Relay FaultThe eps relay is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BatCon Dir FaultFault |
BatCon Dir FaultThe battery connection is reversed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Relay FaultWarning |
Grid Relay FaultThe grid relay keeps open or close. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| RDSP SPI FaultWarning |
RDSP SPI FaultThe communication between master and slave is fail. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| RDSP Smpl FaultFault |
RDSP Smpl FaultThe slave sample detection circuit is failed. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| ARM EEPROM FaultFault |
ARM EEPROM FaultThe manager eeprom is fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Meter Lost FaultWarning |
Meter Lost FaultThe communication between meter and inverter is interrupted. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BMS LostFault |
BMS LostThe communication between BMS and inverter is interrupted. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Ext FaultFault |
Bms Ext FaultThe communication between BMS and inverter is interrupted. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Int FaultFault |
Bms Int FaultDIP switch at the wrong position; The communication between battery packs is interrupted. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Volt HighFault |
Bms Volt HighBattery over voltage. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Volt LowInfo |
Bms Volt LowBattery under voltage. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms ChgCur HighFault |
Bms ChgCur HighBattery charge over current. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms DchgCur HighFault |
Bms DchgCur HighBattery discharge over current. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Temp HighSafety-Critical |
Bms Temp HighBattery over temperature. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Temp LowSafety-Critical |
Bms Temp LowBattery under temperature. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BmsCellImbalanceWarning |
BmsCellImbalanceThe capacities of cells are different. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms HW ProtectFault |
Bms HW ProtectBattery hardware under protection. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BmsCircuit FaultWarning |
BmsCircuit FaultBms hardware circuit fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Insul FaultSafety-Critical |
Bms Insul FaultBattery insulation fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BmsVoltsSen FaultFault |
BmsVoltsSen FaultBattery voltage sensor fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BmsTempSen FaultSafety-Critical |
BmsTempSen FaultBattery temperature sensor fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| BmsCurSen FaultFault |
BmsCurSen FaultBattery current sensor fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Relay FaultFault |
Bms Relay FaultBattery relay fault. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Type UnmatchFault |
Bms Type UnmatchThe capacity of battery packs is different. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Ver UnmatchFault |
Bms Ver UnmatchThe software between slaves are different. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms Mfg UnmatchFault |
Bms Mfg UnmatchThe cell manufacture is different. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms SwHw UnmatchFault |
Bms SwHw UnmatchThe slave software and hardware are not match. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms M&S UnmatchFault |
Bms M&S UnmatchThe software between Master and Slave are not match. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bms ChgReq NoAckInfo |
Bms ChgReq NoAckNo action for charging request. What you can do
H3/AC3 three-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Lost FaultInfo |
Grid Lost FaultGrid Lost Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Volt FaultWarning |
Grid Volt FaultGrid Volt Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Grid Freq FaultWarning |
Grid Freq FaultGrid Freq Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| 10min Volt FaultFault |
10min Volt Fault10min Volt Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Inv Cur FaultFault |
SW Inv Cur FaultSW Inv Cur Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| DCI FaultFault |
DCI FaultDCI Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| HW Inv Cur FaultFault |
HW Inv Cur FaultHW Inv Cur Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| SW Bus Vol FaultFault |
SW Bus Vol FaultSW Bus Vol Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| Bat Volt FaultFault |
Bat Volt FaultBat Volt Fault What you can do
KH/KA single-phase hybrid & AC-coupled · Guide only. All work must be done by a licensed electrician. |
| OffFault |
OffOn for 1s, Off for 1s What you can do
ECS series battery (ECS2900/4100 etc.) · Guide only. All work must be done by a licensed electrician. |
| LED: =100%Info |
=100%=100% (shown as S LED solid; SOC LEDs 4-1: on on on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Under voltage faultInfo |
Under voltage faultUnder voltage fault (shown as S LED flashing; SOC LEDs 4-1: off off off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Over voltage faultInfo |
Over voltage faultOver voltage fault (shown as S LED flashing; SOC LEDs 4-1: off off on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Over temperature faultInfo |
Over temperature faultOver temperature fault (shown as S LED flashing; SOC LEDs 4-1: off off on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Under temperature faultInfo |
Under temperature faultUnder temperature fault (shown as S LED flashing; SOC LEDs 4-1: off on off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Discharge over currentInfo |
Discharge over currentDischarge over current (shown as S LED flashing; SOC LEDs 4-1: off on off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Charge over currentInfo |
Charge over currentCharge over current (shown as S LED flashing; SOC LEDs 4-1: off on on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Parallel addressing failureInfo |
Parallel addressing failureParallel addressing failure (shown as S LED flashing; SOC LEDs 4-1: on off off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Pre-Charge failedInfo |
Pre-Charge failedPre-Charge failed (shown as S LED flashing; SOC LEDs 4-1: on off off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Short circuit protectionInfo |
Short circuit protectionShort circuit protection (shown as S LED flashing; SOC LEDs 4-1: on off on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: AFE communication failedWarning |
AFE communication failedAFE communication failed (shown as S LED flashing; SOC LEDs 4-1: on off on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Module addressing failedInfo |
Module addressing failedModule addressing failed (shown as S LED flashing; SOC LEDs 4-1: on on off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Internal communication failedWarning |
Internal communication failedInternal communication failed (shown as S LED flashing; SOC LEDs 4-1: on on off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Power parallel failureInfo |
Power parallel failurePower parallel failure (shown as S LED flashing; SOC LEDs 4-1: on on on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: PCS communication failedWarning |
PCS communication failedPCS communication failed (shown as S LED flashing; SOC LEDs 4-1: on on on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: HVB FUSE faultInfo |
HVB FUSE faultHVB FUSE fault (shown as S LED solid; SOC LEDs 4-1: off off off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Current sampling faultInfo |
Current sampling faultCurrent sampling fault (shown as S LED solid; SOC LEDs 4-1: off off on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Module not matchInfo |
Module not matchModule not match (shown as S LED solid; SOC LEDs 4-1: off off on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Internal total voltage sampling failedInfo |
Internal total voltage sampling failedInternal total voltage sampling failed (shown as S LED solid; SOC LEDs 4-1: off on off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Temperature sampling failedInfo |
Temperature sampling failedTemperature sampling failed (shown as S LED solid; SOC LEDs 4-1: off on off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Relay adhesionInfo |
Relay adhesionRelay adhesion (shown as S LED solid; SOC LEDs 4-1: off on on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Relay not closeInfo |
Relay not closeRelay not close (shown as S LED solid; SOC LEDs 4-1: off on on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Relay drive failedInfo |
Relay drive failedRelay drive failed (shown as S LED solid; SOC LEDs 4-1: on off off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Cell "0V" faultInfo |
Cell "0V" faultCell "0V" fault (shown as S LED solid; SOC LEDs 4-1: on off off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Temperature high permanent failedInfo |
Temperature high permanent failedTemperature high permanent failed (shown as S LED solid; SOC LEDs 4-1: on off on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: The single voltage high permanently failedInfo |
The single voltage high permanently failedThe single voltage high permanently failed (shown as S LED solid; SOC LEDs 4-1: on off on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: SOH low protectionInfo |
SOH low protectionSOH low protection (shown as S LED solid; SOC LEDs 4-1: on on off off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: AFE failed (UV/OV/UT/OT)Info |
AFE failed (UV/OV/UT/OT)AFE failed (UV/OV/UT/OT) (shown as S LED solid; SOC LEDs 4-1: on on off on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Charger overvoltageInfo |
Charger overvoltageCharger overvoltage (shown as S LED solid; SOC LEDs 4-1: on on on off). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
| LED: Other faultInfo |
Other faultOther fault (shown as S LED solid; SOC LEDs 4-1: on on on on). Flashing S LED = alarm/protection, solid = fault. What you can do
EP5/EP11 battery · Guide only. All work must be done by a licensed electrician. |
No codes match. Try fewer characters, or ask us.
Common FoxESS questions
What does FoxESS SW Inv Cur Fault "Output current high (software)" mean?
The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does FoxESS DCI Fault "DC component in output current out of limit" mean?
The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. If it happened once and the system recovered, keep an eye on it This is a guide only; any electrical work must be done by a licensed electrician.
What does FoxESS HW Inv Cur Fault "Output current high (hardware)" mean?
The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does FoxESS SW Bus Vol Fault "Bus voltage out of range (software)" mean?
The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. Note the code, time and whether it clears by itself This is a guide only; any electrical work must be done by a licensed electrician.
What does FoxESS Bat Volt Fault "Battery voltage fault" mean?
The battery management system has reported a problem with battery voltage, current, cells or internal hardware and has limited or stopped battery operation. Do not open the battery or touch its terminals This is a guide only; any electrical work must be done by a licensed electrician.
Need help with this fault?
Get a licensed electrician to call you back.
Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.
Or call 1300 209 503
Sources
Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.
- FoxESS H1(G2)/AC1(G2) Series User Manual, AU, V1.0.0 (10-500-10582-00, 2026-05-11), section 9.1 Alarm List
- FoxESS H3-Plus User Manual (AU, 2026-03-16), section 9.2 Alarm List
- FoxESS H3/AC3 Series User Manual V1.0.4 (2025-01-07), Alarm List
- FoxESS KH/KA User Manual V1.0.6 (AU), 9.1 Alarm List
- FoxESS ECS User Manual (AU, 10-500-10068-01)
- FoxESS EP5/EP11 User Manual V1.0.6, fault status indicated by indicator
FoxESS is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides