Growatt MOD TL3-X (three-phase) error codes explained
What 63 Growatt MOD TL3-X (three-phase) inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.
Safety first: never open the switchboard, remove covers, or pull apart or disconnect the inverter, batteries, isolators or wiring. Only use the switches and buttons described here. Anything else must be done by a licensed electrician. Call 1300 209 503 or book a service request.
| Code | Message & meaning |
|---|---|
| Warning 200Warning |
String faultOne solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 201Fault |
String PID quick-connect terminal detection errorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 202Fault |
DC SPD function abnormalA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 203Fault |
PV circuit shortA solar string or the battery appears to be connected with positive and negative swapped. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 204Info |
Dry contact function abnormalThe system has received a shutdown or control signal, or a protective input has been triggered (for example an emergency stop, demand response or external switch). What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 205Fault |
PV boost driver brokenThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 206Fault |
AC SPD function abnormalA surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 207Info |
USB (U disk) over-current protectionA monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 208Fault |
DC fuse openThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 209Fault |
DC input voltage exceeds maximumThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 210Fault |
PV reversedA solar string or the battery appears to be connected with positive and negative swapped. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 300Warning |
No utilityThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 301Warning |
Grid voltage out of rangeThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 302Warning |
Grid frequency out of rangeGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 303Warning |
EPS mode overloadThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 304Warning |
CT open or wrongThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 305Warning |
CT line reversed or ground failThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 306Warning |
Communication fault: M3 didn't receive SP-CT dataThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 307Fault |
Communication faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 400Warning |
Fan function abnormalA cooling fan isn't working properly, which can make the unit run hot and reduce output. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 401Warning |
Meter abnormalThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 402Fault |
Optimiser and inverter communication abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 403Fault |
String communication abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 404Fault |
EEPROM abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 405Fault |
DSP and COM firmware version unmatchThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Warning 406Fault |
Boost module errorThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 200Critical |
AFCI faultThe inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 201Critical |
Leakage current too highThe inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 202Fault |
DC input voltage exceeds maximumThe DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 203Critical |
PV isolation lowThe inverter measured low insulation resistance between the solar/battery DC circuits and earth. In Australia this is treated as an earth fault alarm, and the system must be checked by a licensed electrician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 300Warning |
AC V OutrangeThe mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 301Fault |
AC terminals reversedThe inverter has detected an AC wiring problem, for example active and neutral swapped or a connection made the wrong way round. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 302Warning |
No AC connectionThe inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup). What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 303Critical |
NE abnormalThe inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 304Warning |
AC F OutrangeGrid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 305Warning |
Overload faultThe backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 306Warning |
CT LN reversedThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 307Warning |
Communication fault: M3 didn't receive SP-CT dataThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 308Warning |
Communication fault: pairing time too longThe inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 400Fault |
DCI bias abnormalThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 401Fault |
DC voltage high faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 402Fault |
Output DC current too highThe inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 403Fault |
Output current unbalanceThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 404Fault |
Bus sample faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 405Fault |
Relay faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 406Fault |
Init model faultThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 407Fault |
Auto test failureThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 408Warning |
NTC temperature too highThe inverter is running too hot, so it has reduced output or paused to protect itself. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 409Fault |
Bus voltage abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 410Fault |
Communication board / control panel battery-voltage sampling inconsistentThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 411Fault |
Communication faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 412Fault |
Temperature sensor connection abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 413Fault |
IGBT drive faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 414Fault |
EEPROM faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 415Fault |
Internal power test fail (PV power low)The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 416Fault |
Overcurrent protected by softwareThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 417Fault |
Grid voltage sampling inconsistentThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 418Fault |
DSP and COM firmware version unmatchThere is a firmware, model or configuration mismatch between parts of the system, so it can't run normally. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 419Fault |
Inconsistent leakage current samplingThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 420Fault |
GFCI module damageThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 421Fault |
CPLD abnormalThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 422Fault |
Sampling inconsistentThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
| Error 425Fault |
AFCI self-test faultThe equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician. What you can do
MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician. |
No codes match. Try fewer characters, or ask us.
Need help with this fault?
Get a licensed electrician to call you back.