Growatt MOD TL3-X (three-phase) error codes explained

What 63 Growatt MOD TL3-X (three-phase) inverter & battery fault and error codes mean, in plain English, with safe checks you can do and when to call a licensed electrician.

Guide only. This information is a general guide taken from manufacturer documentation. All electrical work must be performed by a licensed electrician. Never open your inverter, battery or switchboard. If you see smoke, smell burning or see damage, keep clear and call 000.
CodeMessage & meaningModelType
Warning 200Warning
String fault

One solar string is behaving differently from the others (lower output or current flowing the wrong way), which often points to a panel, connector or configuration issue.

What you can do

  • From the ground, check for new shading (trees, new structures) or obvious debris
  • Compare string readings in your monitoring app if available
  • Book a service check if it continues

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 201Fault
String PID quick-connect terminal detection error

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 202Fault
DC SPD function abnormal

A surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge.

What you can do

  • Don't open the inverter
  • Call us. SPDs must be replaced by a licensed electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 203Fault
PV circuit short

A solar string or the battery appears to be connected with positive and negative swapped.

What you can do

  • Do not touch any DC wiring
  • Call us or a licensed electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 204Info
Dry contact function abnormal

The system has received a shutdown or control signal, or a protective input has been triggered (for example an emergency stop, demand response or external switch).

What you can do

  • Check whether anyone operated an emergency stop or shutdown switch on purpose
  • If so, follow the manual to release it only when it is safe
  • If nobody did, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 205Fault
PV boost driver broken

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 206Fault
AC SPD function abnormal

A surge protection device (SPD) inside or connected to the inverter is reporting a fault, often after a lightning storm or grid surge.

What you can do

  • Don't open the inverter
  • Call us. SPDs must be replaced by a licensed electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 207Info
USB (U disk) over-current protection

A monitoring or communication accessory (Wi-Fi/4G/data logger, display or clock) is reporting a problem. This usually doesn't stop the system generating.

What you can do

  • Restart your home router and check it reaches the inverter location
  • If you changed router or Wi-Fi password, the dongle needs reconfiguring (see the manufacturer's app guide or ask us)
  • If generation looks normal but the alarm persists, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 208Fault
DC fuse open

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 209Fault
DC input voltage exceeds maximum

The DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter.

What you can do

  • Do not touch the DC isolator or cables unless the manufacturer's owner shutdown tells you to
  • Call us. The string design needs to be checked by a licensed installer

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 210Fault
PV reversed

A solar string or the battery appears to be connected with positive and negative swapped.

What you can do

  • Do not touch any DC wiring
  • Call us or a licensed electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 300Warning
No utility

The inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup).

What you can do

  • Check whether the rest of the house (or your neighbours) has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar supply main switch or inverter breaker. Only reset it once. If it trips again, leave it off and call an electrician
  • Wait. Once normal grid power is back, the inverter normally reconnects by itself after its safety checks (often a few minutes)
  • If grid power is normal but the alarm stays, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 301Warning
Grid voltage out of range

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 302Warning
Grid frequency out of range

Grid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require.

What you can do

  • Wait for automatic reconnection
  • If it happens often, record the times and contact us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 303Warning
EPS mode overload

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 304Warning
CT open or wrong

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 305Warning
CT line reversed or ground fail

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 306Warning
Communication fault: M3 didn't receive SP-CT data

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 307Fault
Communication fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 400Warning
Fan function abnormal

A cooling fan isn't working properly, which can make the unit run hot and reduce output.

What you can do

  • From outside, check that nothing is blocking the vents
  • Don't open the unit
  • Call us to arrange a fan check or replacement

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 401Warning
Meter abnormal

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 402Fault
Optimiser and inverter communication abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 403Fault
String communication abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 404Fault
EEPROM abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 405Fault
DSP and COM firmware version unmatch

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Warning 406Fault
Boost module error

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 200Critical
AFCI fault

The inverter's arc-fault detection has picked up a pattern that looks like electrical arcing on the DC (solar) side, which can be a fire risk. The inverter shuts down DC power flow as a precaution.

What you can do

  • Do not reset it repeatedly and do not touch DC cables or isolators
  • If you see smoke or flames or smell burning, keep clear and call 000
  • Call us or a licensed electrician to inspect the DC wiring before the system is restarted

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 201Critical
Leakage current too high

The inverter measured leakage (residual) current flowing to earth above its safety limit and disconnected. This can indicate damaged insulation somewhere in the system.

What you can do

  • Don't touch cabling or equipment
  • If it happens repeatedly, or together with an insulation/isolation alarm, call an electrician or us promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 202Fault
DC input voltage exceeds maximum

The DC voltage coming from the solar panels is higher than the inverter is rated for. Over-voltage can damage the inverter.

What you can do

  • Do not touch the DC isolator or cables unless the manufacturer's owner shutdown tells you to
  • Call us. The string design needs to be checked by a licensed installer

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 203Critical
PV isolation low

The inverter measured low insulation resistance between the solar/battery DC circuits and earth. In Australia this is treated as an earth fault alarm, and the system must be checked by a licensed electrician.

What you can do

  • Do not touch panels, DC cables, rooftop isolators or the inverter's DC connectors
  • If it clears by itself after the weather dries out, still report it, because repeated alarms point to a developing fault
  • Book an electrician or call us. An insulation test needs specialist equipment
  • If you see smoke, burn marks or smell burning, keep clear and call 000

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 300Warning
AC V Outrange

The mains voltage the inverter measured was outside the limits allowed for your network, so it disconnected or reduced output to protect the grid. This is usually a grid condition, not a faulty inverter.

What you can do

  • Wait. The inverter reconnects by itself once voltage is back within limits
  • Note the time of day it happens. If it happens most sunny days, tell us, because it may need a voltage check or a report to your network operator
  • Don't try to change grid protection settings yourself. In Australia they are set to AS/NZS 4777.2 and your network operator's requirements

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 301Fault
AC terminals reversed

The inverter has detected an AC wiring problem, for example active and neutral swapped or a connection made the wrong way round.

What you can do

  • Do not touch any wiring
  • Leave the system as it is and book a licensed electrician (or call us)

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 302Warning
No AC connection

The inverter cannot see a normal mains supply, so it has stopped exporting to the grid (and a hybrid system may switch to backup).

What you can do

  • Check whether the rest of the house (or your neighbours) has power, and check your network operator's outage map
  • Check the switchboard for a tripped solar supply main switch or inverter breaker. Only reset it once. If it trips again, leave it off and call an electrician
  • Wait. Once normal grid power is back, the inverter normally reconnects by itself after its safety checks (often a few minutes)
  • If grid power is normal but the alarm stays, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 303Critical
NE abnormal

The inverter detected a problem with the earth (protective earth/PE) or with the neutral-to-earth connection. A sound earth is essential for electrical safety.

What you can do

  • Do not touch the inverter, frames or cabling
  • Leave the system off if it has shut down. Call a licensed electrician or us to test the earthing

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 304Warning
AC F Outrange

Grid frequency moved outside the allowed range, so the inverter disconnected or reduced output as the standards require.

What you can do

  • Wait for automatic reconnection
  • If it happens often, record the times and contact us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 305Warning
Overload fault

The backup/EPS (off-grid) output is overloaded or abnormal, so the system has limited or switched off backup power.

What you can do

  • Switch off large appliances on backup circuits
  • Wait for the system to retry (some models lock out for a period after repeated overloads)
  • If it trips with only small loads on, or you suspect a short circuit, call an electrician

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 306Warning
CT LN reversed

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 307Warning
Communication fault: M3 didn't receive SP-CT data

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 308Warning
Communication fault: pairing time too long

The inverter isn't getting correct readings from its energy meter or current sensor (CT). This affects export limiting, battery charging and monitoring accuracy.

What you can do

  • Check the app. Generation may still be running normally
  • Don't open the switchboard
  • Call us to check the meter/CT wiring. If your system has an export limit, this needs fixing promptly

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 400Fault
DCI bias abnormal

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 401Fault
DC voltage high fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 402Fault
Output DC current too high

The inverter detected too much DC current in its AC output, which the grid standards don't allow, so it disconnected.

What you can do

  • If it happened once and the system recovered, keep an eye on it
  • If it repeats, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 403Fault
Output current unbalance

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 404Fault
Bus sample fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 405Fault
Relay fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 406Fault
Init model fault

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 407Fault
Auto test failure

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 408Warning
NTC temperature too high

The inverter is running too hot, so it has reduced output or paused to protect itself.

What you can do

  • Make sure nothing is stacked against or in front of the inverter, and leave the manufacturer's clearances around it
  • Gently clear dust or leaves from the outside of the vents, without opening the unit or spraying water
  • Let it cool. It normally resumes by itself
  • If it keeps happening on mild days, call us

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 409Fault
Bus voltage abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 410Fault
Communication board / control panel battery-voltage sampling inconsistent

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 411Fault
Communication fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 412Fault
Temperature sensor connection abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 413Fault
IGBT drive fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 414Fault
EEPROM fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 415Fault
Internal power test fail (PV power low)

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 416Fault
Overcurrent protected by software

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 417Fault
Grid voltage sampling inconsistent

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 418Fault
DSP and COM firmware version unmatch

There is a firmware, model or configuration mismatch between parts of the system, so it can't run normally.

What you can do

  • Don't try to reflash firmware yourself unless the manufacturer's app tells you to and it's an owner function
  • Call us. We can arrange a firmware update or reconfiguration with the manufacturer

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 419Fault
Inconsistent leakage current sampling

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 420Fault
GFCI module damage

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 421Fault
CPLD abnormal

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 422Fault
Sampling inconsistent

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter
Error 425Fault
AFCI self-test fault

The equipment's self-checks found an internal problem (for example relays, measuring circuits, internal communication or power electronics). Some of these clear by themselves after a one-off event, but repeated alarms usually need a technician.

What you can do

  • Note the code, time and whether it clears by itself
  • If your installer showed you the owner shutdown/restart procedure from the manufacturer's manual (summarised at the top of this page), you may restart the system once. Do not open covers or touch cabling.
  • If the code returns or the system stays offline, call us. Internal faults are a warranty/technician job

MOD TL3-X (three-phase) · Guide only. All work must be done by a licensed electrician.

MOD TL3-X (three-phase) Inverter

Need help with this fault?

Get a licensed electrician to call you back.

Total Solar can help: our licensed electricians install and service systems. Based in Ellenbrook, WA, with Victoria and Queensland also available.

Or call 1300 209 503

By sending this form you agree to Total Solar (THK Group Pty Ltd) contacting you by phone, SMS or email about this request. We use your details only to respond, as set out in our Privacy Policy.

Sources

Meanings are summarised from these manufacturer documents. Check your own model's manual, as codes vary between models and firmware versions.

Growatt is a trademark of its owner. Total Solar is not affiliated with the manufacturer unless stated. All fault code guides